Skip to main content
Schneider Electric A9F04320 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F04320 Acti9 iC60 MCB, 20 A, C-Curve, 3

MPNA9F04320
Active

Schneider Electric Acti9 iC60, miniature circuit breaker, 3P, 20 A, C-curve, 36 kA Icu at 133 V AC, DIN rail mount, white.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F04320 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F04320 — Ratings
ParameterValue
Rated current (In)20 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F04320 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F04320 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F04320 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F04320 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

What this MCB does for your panel

The Schneider Electric A9F04320 is a 3-pole Acti9 iC60 miniature circuit breaker rated at 20 A with a C-curve trip characteristic. Breaking capacity reaches 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, and 10 kA at 380–415 V AC per EN/IEC 60947-2. At 400 V AC under EN/IEC 60898-1 it delivers 10 kA Icn. That SCCR headroom lets you coordinate downstream without cascading upstream — useful for a panel feeding multiple sub-distribution boards.

Occupies 6 × 9 mm pitches (54 mm wide) — a compact 3-pole footprint for a 20 A device. Height 91 mm, depth 78.5 mm — fits most enclosure depths without crowding the gland plate. Tightening torque 2 N·m; strip length 14 mm. Spring-cage or screw? Toggle control, so it's a manual-break switch with a trip indicator and contact position indicator for safe isolation verification.

Frequently asked questions

What is the breaking capacity of A9F04320 at 400 V?

At 400 V AC under EN/IEC 60898-1 it delivers 10 kA Icn; under EN/IEC 60947-2 at 380–415 V AC it is rated 10 kA Icu.

What compliance documentation is available for A9F04320?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, carries IP20 protection, and is tropicalised per IEC 60068-1 (class 2). RoHS and REACH declarations are standard for the Acti9 range.

Where can I buy the A9F04320?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

MPN
A9F04320