Skip to main content
Schneider Electric A9F04406 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F04406 Acti9 iC60N MCB, 6 A, C Curve, 4

MPNA9F04406
Active

Schneider Electric Acti9 iC60N miniature circuit-breaker, A9F04406, 6 A rated current, C curve, 4 poles, breaking capacity 36 kA Icu at 12-133 V AC, dual-rated to EN/IEC 60947-2 and EN/IEC 60898-1.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F04406 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F04406 — Ratings
ParameterValue
Rated current (In)6 A
Poles configuration4P
Number of protected poles4
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F04406 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F04406 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F04406 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F04406 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F04406 is a 6 A, C-curve, 4-pole miniature circuit-breaker from the Schneider Electric Acti9 iC60N range. At 400 V AC, the Icn is 10 kA per EN/IEC 60898-1; the Icu per EN/IEC 60947-2 reaches 36 kA at 12-133 V AC, 20 kA at 220-240 V, 10 kA at 380-415 V, and 6 kA at 440 V. The 4-pole configuration with 4 protected poles and a separate earth-leakage block option makes it appropriate for three-phase plus neutral distribution in panelboards where isolation is required — the breaker is marked suitable for isolation per both standards.

Mounts on DIN rail (9 mm pitch, 8 pitches wide = 72 mm). The thermal-magnetic trip unit is sealed; no field adjustment. Wire stripping length is 14 mm. IP20 finger-safe terminals. The white housing includes a trip indicator and contact position indicator.

Frequently asked questions

What is A9F04406's breaking capacity at 400 V?

At 400 V AC 50/60 Hz, the Icn per EN/IEC 60898-1 is 10 kA. The Icu per EN/IEC 60947-2 is 10 kA at 380-415 V and 6 kA at 440 V.

What compliance documentation does this brand provide for A9F04406?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries a suitability-for-isolation marking per both standards. The evidence does not list RoHS, REACH, or UL documentation, but these are typically available from the manufacturer upon request.

Where can I buy A9F04406 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is listed here.

MPN