Skip to main content
Schneider Electric A9F04432 — Miniature Circuit Breakers (MCB)

Schneider A9F04432 Acti9 iC60N MCB, 32 A, C-Curve, 4P, 10 kA

MPNA9F04432
Active

Schneider Electric Acti9 iC60N, A9F04432, miniature circuit-breaker, 4P, 32 A, C-curve, 10 kA Icn at 400 V AC, thermal-magnetic, DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F04432 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F04432 — Ratings
ParameterValue
Rated current (In)32 A
Poles configuration4P
Number of protected poles4
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F04432 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F04432 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F04432 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F04432 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

32 A C-curve MCB for distribution boards

The Schneider A9F04432 is an Acti9 iC60N miniature circuit-breaker rated 32 A with a C-curve magnetic trip at 8 x In (+/- 20 %). Four poles, thermal-magnetic trip unit, DIN-rail mount. Dual-rated to EN/IEC 60947-2 (Category A) and EN/IEC 60898-1, so it carries both the industrial and residential certification — useful when the same BOM feeds panel builds and final distribution boards.

Breaking capacity follows the voltage: 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, 6 kA at 440 V (all per EN/IEC 60947-2). The IEC 60898-1 rating is 10 kA Icn at 400 V AC — that's the number most distribution specs will reference. Overvoltage category IV, pollution degree 3, so it's rated for the mains entry, not just sub-distribution.

Lifecycle stage is current — no NRND or phase-out signal on this order code. The Acti9 iC60 series is Schneider's mainstream MCB line; the A9F04432 is an active catalog number.

Mounts on DIN rail, 9 mm pitches: 8 modules wide (72 mm). Height 91 mm, depth 78.5 mm. Tightening torque 3.5 N·m. Wire strip length 14 mm. IP20 finger-safe. The white body with toggle and trip indicator makes visual status checks fast during commissioning or fault-finding.

Electrical endurance 10,000 cycles, mechanical 20,000 cycles. Rated for isolation per both IEC 60898-1 and 60947-2 — the contact position indicator and positive break confirm the circuit is open. Suits non-condensing environments in panel builds for industrial or commercial distribution.

Frequently asked questions

Where can I buy the A9F04432 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead time and price.

What is the breaking capacity of the A9F04432 at 400 V?

10 kA Icn at 400 V AC per EN/IEC 60898-1. Per EN/IEC 60947-2, the Icu at 380–415 V AC is also 10 kA.

What standards does the A9F04432 comply with?

Dual-rated to EN/IEC 60947-2 and EN/IEC 60898-1. Also conforms to IEC 60529 (IP20), IEC 60068-1 (tropicalisation class 2), and pollution degree 3 per EN/IEC 60947-2.

What is the magnetic trip threshold on the A9F04432?

C-curve: magnetic tripping at 8 x In +/- 20 %. For the 32 A rating, that's 256 A nominal, with a tolerance band of roughly 205–307 A.

MPN
A9F04432