The Schneider Electric A9F04702 is an Acti9 iC60N miniature circuit breaker rated 2 A with a C-curve (magnetic trip at 8 x In ±20%, so 16 A typical instantaneous pickup). The same part is also rated 6 kA Icn at 400 V per EN/IEC 60898-1, the domestic-standard marking. Dual-rated means it qualifies for both industrial (60947-2) and residential/commercial (60898-1) installations — useful when a BOM crosses building code boundaries. The neutral position is left, which matters when aligning busbar comb fingers in a multi-pole assembly. DIN-rail mount, 72 mm wide (8 x 9 mm pitches), so it occupies standard panel space.
Integration notes
Tightening torque 2 N·m. Wire strip length 14 mm. IP20 finger-safe front, pollution degree 3 (conductive pollution environment, typical for industrial panels). Overvoltage category IV — suitable for main incoming supply.