Skip to main content
Schneider Electric A9F04706 — Miniature Circuit Breakers (MCB)

A9F04706 Acti9 iC60 MCB, 6 A, Curve C, 3P+N, 36 kA

MPNA9F04706
Active

Schneider Electric Acti9 iC60N miniature circuit breaker, A9F04706, 6 A rated, C-curve, 3P+N, 36 kA Icu at 133 V AC, DIN rail mount, thermal-magnetic trip, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F04706 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F04706 — Ratings
ParameterValue
Rated current (In)6 A
Poles configuration3P + N
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F04706 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F04706 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F04706 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F04706 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F04706 is an Acti9 iC60 miniature circuit breaker — a 6 A, C-curve, 3P+N unit built for distribution panels. It sits on a standard DIN rail, occupying 8 x 9 mm pitches (72 mm wide), with a depth of 78.5 mm and height of 91 mm. That footprint fits neatly into a crowded enclosure; the toggle and trip indicator are visible through the door.

The breaking capacity tells the real story: 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V AC. That's enough SCCR headroom for most panelboards fed from a transformer; the 6000 A Icn at 400 V (EN/IEC 60898-1) is the domestic-application ceiling. Dual-certified to EN/IEC 60947-2 and 60898-1, so it qualifies as both an industrial circuit breaker and a domestic MCB — useful when a single BOM covers both standards.

Integration notes

Frequently asked questions

Where can I buy A9F04706?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What is the breaking capacity of A9F04706?

36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V AC per EN/IEC 60947-2; also 6000 A Icn at 400 V per EN/IEC 60898-1.

What standards does A9F04706 comply with?

It is certified to EN/IEC 60947-2 (industrial circuit breaker) and EN/IEC 60898-1 (domestic MCB). Also carries IP20 protection, pollution degree 3, overvoltage category IV, and tropicalisation class 2 per IEC 60068-1.

MPN
A9F04706