Schneider Electric A9F04713 — Miniature Circuit Breakers (MCB)

A9F04713 Acti9 iC60 MCB, 13 A, C curve, 3P+N, 36 kA

MPNA9F04713
Active

Schneider Electric Acti9 iC60, miniature circuit-breaker, A9F04713, 13 A, C curve, 3P+N, 36 kA breaking capacity.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F04713 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F04713 — Ratings
ParameterValue
Rated current (In)13 A
Poles configuration3P + N
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F04713 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F04713 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F04713 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F04713 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F04713 is an Acti9 iC60 miniature circuit-breaker (MCB) rated 13 A with a C curve, thermal-magnetic trip, and 3 protected poles plus neutral (3P+N).

Snaps onto a DIN rail — standard 9 mm pitch, 8 modules wide (72 mm). Height is 91 mm, depth 78.5 mm. That's a compact footprint for a 3P+N breaker; you'll fit it into a 4-row enclosure without crowding. Neutral is on the left. IP20 rated — fine inside a panel, not for wet locations. Overvoltage category IV means it's rated for installation at the service entrance, not just downstream subpanels.

Dual-certified to EN/IEC 60898-1 and EN/IEC 60947-2. Suitability for isolation is confirmed under both standards — you can safely use it as a disconnecting means.

Frequently asked questions

What is A9F04713's breaking capacity?

Breaking capacity is 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V AC, 10 kA at 380–415 V AC, 6 kA at 440 V AC, and 6000 A Icn at 400 V per EN/IEC 60898-1.