Skip to main content
Schneider Electric A9F04720 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F04720 Acti9 iC60N MCB, 20 A, 3P+N, C-C

MPNA9F04720
Active

Schneider Electric Acti9 iC60N, miniature circuit breaker, 20 A, 3P+N, C-curve, breaking capacity 36 kA Icu at 12-133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F04720 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F04720 — Ratings
ParameterValue
Rated current (In)20 A
Poles configuration3P + N
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F04720 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F04720 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F04720 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F04720 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

Acti9 iC60N — 20 A, 3P+N, C-Curve MCB

The Schneider Electric A9F04720 is a 20 A, 3P+N miniature circuit breaker from the Acti9 iC60N series, with a C-curve trip characteristic. Rated for both AC and DC networks at 50/60 Hz, this MCB carries a breaking capacity of 36 kA Icu at 12-133 V AC, 20 kA Icu at 220-240 V AC, 10 kA Icu at 380-415 V AC, and 6 kA Icu at 440 V AC, per EN/IEC 60947-2. The Icn rating per EN/IEC 60898-1 is 6000 A at 400 V AC. The C-curve means magnetic tripping occurs at 8 x In ±20%, suitable for circuits with moderate inrush currents like lighting or small motor loads. The 3P+N configuration protects three phases with a switched neutral on the left side. Overvoltage category IV and pollution degree 3 ratings confirm it is suitable for main distribution panels in industrial environments. The IP20 finger-safe enclosure is standard for panel-mount breakers; no washdown rating.

Panel Integration

Occupies 8 x 9 mm pitches (72 mm) on the DIN rail. The 78.5 mm depth leaves clearance for standard enclosure depths. Double terminals top and bottom accept 1-25 mm² rigid or 1-16 mm² flexible conductors.

Frequently asked questions

Where can I buy the A9F04720?

The A9F04720 is sourced and quoted to order against an RFQ through independent distribution. Availability and pricing are confirmed at quote time.

What is the breaking capacity of the A9F04720?

The breaking capacity is 36 kA Icu at 12-133 V AC, 20 kA Icu at 220-240 V AC, 10 kA Icu at 380-415 V AC, and 6 kA Icu at 440 V AC per EN/IEC 60947-2. The Icn rating per EN/IEC 60898-1 is 6000 A at 400 V AC.

What standards does the A9F04720 comply with?

It complies with EN/IEC 60947-2 and EN/IEC 60898-1, and is suitable for isolation per both standards. It also conforms to IEC 60068-1 for tropicalisation (class 2) and IEC 60529 for IP20 protection.

MPN
A9F04720