The A9F04770 is a Schneider Electric Acti9 iC60 miniature circuit-breaker (MCB) rated at 0.5 A with a C-curve, 3 poles plus neutral, and a breaking capacity of 50 kA Icu at 415 V AC. The C-curve magnetic trip operates at 8 x In ±20 % per the spec.
Rated Icu of 50 kA at 220–415 V AC per EN/IEC 60947-2, with a 6000 A Icn per EN/IEC 60898-1 at 400 V. The dual rating means it qualifies for both industrial (60947-2) and residential/commercial (60898-1) applications — useful when the same panel feeds mixed loads and the inspector wants a single part number for the BOM. Overvoltage category IV means it can be installed at the service entrance or main distribution board.
Integration notes
The 72 mm width (8 x 9 mm pitches) fits a standard 4-module slot in a distribution board. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible wire; strip length 14 mm, torque to 2 N·m. The white housing and toggle actuator are standard for the Acti9 range; the trip indicator gives local visual confirmation of a tripped state.