Skip to main content
Schneider Electric A9F05102 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F05102 Acti9 iC60N MCB, 2 A D Curve, 1P

MPNA9F05102
Active

Schneider Electric Acti9 iC60N miniature circuit breaker, A9F05102, 2 A rated, D curve, 1-pole, 50 kA Icu at 240 V AC, thermal-magnetic trip, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F05102 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F05102 — Electrical & Protection
ParameterValue
Rated current (In)2 A
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)50 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F05102 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom

Environmental

A9F05102 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F05102 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F05102 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F05102 is a 2 A, 1-pole miniature circuit breaker from the Acti9 iC60N series, built for distribution boards and panel applications. Its D curve (magnetic trip at 12 x In ±20 %) means it handles high inrush loads — motors, transformers, or switching power supplies — without nuisance tripping on start-up. The thermal-magnetic trip unit covers both overload (thermal bimetal) and short-circuit (solenoid) protection in one 18 mm wide module.

Rated 50 kA Icu at 220–240 V AC (EN/IEC 60947-2) and 6 kA Icn at 230 V AC (EN/IEC 60898-1). Dual-certified to both the industrial (60947-2) and residential (60898-1) standards, so it qualifies for either duty.

Double terminals top and bottom accept 1–25 mm² rigid or 1–16 mm² flexible wire; strip length 14 mm, torque to 2 N·m. IP20 finger-safe terminals — fine for enclosed panels, not for wet environments.

Frequently asked questions

Where can I buy the A9F05102 and get a price?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is the breaking capacity of the A9F05102?

50 kA Icu at 220–240 V AC (EN/IEC 60947-2) and 6 kA Icn at 230 V AC (EN/IEC 60898-1).

MPN
A9F05102