Skip to main content
Schneider Electric A9F05106 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F05106 Acti9 iC60N MCB, 6A D Curve, 1P

MPNA9F05106
Active

Schneider Electric Acti9 iC60N, A9F05106, miniature circuit breaker, 1P, 6 A, D curve, 36 kA breaking capacity, thermal-magnetic trip, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F05106 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F05106 — Electrical & Protection
ParameterValue
Rated current (In)6 A
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F05106 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom

Environmental

A9F05106 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F05106 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F05106 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

At 230 V AC the A9F05106 carries a 6 kA Icn rating per EN/IEC 60898-1, but under EN/IEC 60947-2 it's rated 36 kA Icu at 12-60 V AC, 20 kA at 100-133 V AC, and 10 kA at 220-240 V AC. On the DC side it handles 15 kA at 12-60 V DC and 10 kA at 60-72 V DC. That spread means it can be applied in low-voltage industrial control panels where fault currents are higher than a standard residential panel, and still coordinate with downstream loads.

Snaps onto a standard DIN rail — 18 mm width (2 x 9 mm pitches), 91 mm tall, 78.5 mm deep. The double-terminal design on top and bottom accepts 1-25 mm² rigid or 1-16 mm² flexible, with a stripping length of 14 mm and a tightening torque of 2 Nm. IP20 finger-safe terminals are fine for enclosed panels; keep it behind a door or cover in a washdown area.

Frequently asked questions

Where can I buy the A9F05106 and get a price?

The A9F05106 is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price is published here.

What is the breaking capacity of the A9F05106?

At 230 V AC the breaker is rated 6 kA Icn per EN/IEC 60898-1. Under EN/IEC 60947-2 it achieves 36 kA Icu at 12-60 V AC, 20 kA at 100-133 V AC, and 10 kA at 220-240 V AC. On DC it handles 15 kA at 12-60 V DC and 10 kA at 60-72 V DC.

What standards does the A9F05106 comply with?

It is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with a pollution degree of 3, overvoltage category IV, and suitability for isolation per both standards. Tropicalisation class 2 per IEC 60068-1 is also listed.

What is the D curve on the A9F05106 for?

The D curve trips magnetically at 12 x In (72 A for this 6 A breaker), +/-20%. It is intended for loads with high inrush currents such as small motors, transformers, and solenoid valves where a B or C curve would nuisance-trip on startup.

MPN
A9F05106