Skip to main content
Schneider Electric A9F05113 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F05113 Acti9 iC60N MCB, 13 A, 1P, D Cur

MPNA9F05113
Obsolete

Schneider Electric Acti9 iC60N, A9F05113, miniature circuit breaker, 1P, 13 A, D curve, 10 kA Icn at 230 V AC, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F05113 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameIC60N
Poles description1P
Number of protected poles1
Device applicationDistribution
A9F05113 — Electrical & Protection
ParameterValue
Rated current (In)13 A
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F05113 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9F05113 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F05113 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F05113 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F05113 is an Acti9 iC60N miniature circuit breaker — 1-pole, 13 A rated current, D-curve trip characteristic. On a 230 V AC supply the breaking capacity is 10 kA Icn per EN/IEC 60898-1; at 240 V AC it holds 10 kA Icu per EN/IEC 60947-2. That dual certification (both the household-standard 60898-1 and the industrial-standard 60947-2) lets the same part serve residential distribution boards and industrial panel builds — one BOM line for both worlds.

DIN-rail integration and panel fit

Depth of 78.5 mm and height of 91 mm keep the profile within typical enclosure clearance.

Selectivity and coordination notes

Suitability for isolation (marked per both standards) means it can serve as a disconnecting means in the circuit without a separate isolator.

Frequently asked questions

What is the breaking capacity of A9F05113 at 230 V AC?

10 kA Icn at 230 V AC per EN/IEC 60898-1, and 10 kA Icu at 220–240 V AC per EN/IEC 60947-2.

What compliance documentation does Schneider provide for A9F05113?

The breaker is dual-certified to EN/IEC 60947-2 and EN/IEC 60898-1, carries IP20 protection, and is tropicalised to IEC 60068-1 (class 2).

Where can I buy A9F05113 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock figures or price lists published here.

MPN
A9F05113