The A9F05120 is a 1-pole Acti9 iC60N miniature circuit breaker rated 20 A with a D tripping curve. Breaking capacity is rated per two standards: 36 kA Icu at 12-60 V AC and 10 kA Icu at 220-240 V AC under EN/IEC 60947-2, plus 6 kA Icn at 230 V under EN/IEC 60898-1. The dual rating means this breaker qualifies for industrial panel SCCR calculations (60947-2) and for residential or commercial final-distribution boards (60898-1) — one part covers both compliance paths. Thermal-magnetic trip unit, category A (no intentional short-time delay), so it coordinates as a downstream device in a selective system. Rated insulation voltage 500 V AC, overvoltage category IV — suitable for main incoming panels, not just sub-distribution.
Double terminals top and bottom accept 1-25 mm² rigid or 1-16 mm² flexible — enough for a 20 A feed with parallel outgoing circuits. Tightening torque 2 N.m; strip length 14 mm. IP20 finger-safe terminals, white housing, toggle control with trip-indicator flag. Pollution degree 3, tropicalisation class 2 per IEC 60068-1 — rated for humid, non-condensing panel environments up to 95 % RH at 55 °C.