Skip to main content
Schneider Electric A9F05201 — 2-Pole MCB (DIN Rail)

A9F05201 Acti9 iC60N Miniature Circuit Breaker, 1 A D Curve,

MPNA9F05201
Active

Schneider Electric Acti9 iC60N miniature circuit breaker, A9F05201, 1 A rated current, D tripping curve, 2-pole, 50 kA breaking capacity at 415 V AC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F05201 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameIC60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F05201 — Electrical
ParameterValue
Rated current [In]1 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)DC AC
Network frequency50/60 Hz
A9F05201 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F05201 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F05201 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F05201 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F05201 is a 1 A, D-curve, 2-pole miniature circuit breaker from the Schneider Electric Acti9 iC60 series. At 1 A rated current, this is sized for a small control transformer or a single motor starter, not a feeder. It also carries a 6 kA Icn at 400 V per EN/IEC 60898-1, which is the domestic-standard rating for the same part — the dual standard means it qualifies for both industrial and commercial distribution boards. The thermal-magnetic trip unit is non-interchangeable; the 1 A rating is fixed. IP20 finger-safe terminals accept up to 25 mm² rigid or 16 mm² flexible, with a 14 mm strip length and 2 N·m torque. The toggle provides local signalling via a trip indicator, and the contact position indicator confirms isolation status — it is certified for isolation per both EN/IEC 60898-1 and EN/IEC 60947-2.

Frequently asked questions

Where can I buy A9F05201 and how do I get a price?

The A9F05201 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is A9F05201's listed depth?

The listed depth is 78.5 mm, with a height of 91 mm and width of 36 mm (4 x 9 mm pitches).

What compliance documentation does this brand provide for A9F05201?

The A9F05201 is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with tropicalisation class 2 per IEC 60068-1, pollution degree 3 per EN/IEC 60947-2, and limitation class 3 per EN/IEC 60898-1. It is suitable for isolation per both standards.

MPN