Skip to main content
Schneider Electric A9F05203 — 2-Pole MCB (DIN Rail)

Schneider Electric A9F05203 Acti9 iC60N MCB, D Curve, 3 A, 2

MPNA9F05203
Active

Schneider Electric Acti9 iC60N, miniature circuit breaker, A9F05203, D curve, 3 A, 2P, 50 kA Icu at 415 V AC, DIN rail.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F05203 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameIC60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F05203 — Electrical
ParameterValue
Rated current [In]3 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC DC
Network frequency50/60 Hz
A9F05203 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F05203 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F05203 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F05203 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F05203 is an Acti9 iC60N miniature circuit breaker (MCB) rated 3 A, D curve, 2 poles, designed for distribution in AC and DC networks. The D curve is the key selection parameter here: it allows the breaker to ride through the startup surge without opening, while still providing overcurrent and short-circuit protection.

This MCB carries dual certification to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household / similar). The practical difference: under 60947-2 it is rated 50 kA Icu at 380…415 V AC, which is the ultimate breaking capacity — the breaker can safely interrupt a fault up to 50 kA once and still be functional afterward. Under 60898-1 it is rated 6000 A Icn at 400 V AC, the service breaking capacity for residential-grade coordination. The 2-pole version isolates both phase and neutral in single-phase or DC circuits; the suitability-for-isolation marking confirms it can be used as a disconnecting means per both standards.

The double terminals accept 1…25 mm² rigid or 1…16 mm² flexible, with a stripping length of 14 mm and a tightening torque of 2 N.m. IP20 finger-safe terminals for enclosed panel use. The toggle has a contact position indicator and a separate trip indicator window — useful for quickly identifying a tripped breaker without toggling it. Earth-leakage protection requires a separate Vigi iC60 block; this MCB alone does not provide GFCI.

Frequently asked questions

What is the breaking capacity of the A9F05203 at 415 V?

50 kA Icu at 380…415 V AC per EN/IEC 60947-2. Under EN/IEC 60898-1 the Icn is 6000 A at 400 V AC.

Where can I buy the A9F05203 and how is it quoted?

The A9F05203 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What does the D curve mean on this 3 A breaker?

The D curve means the magnetic trip threshold is 12 x In +/- 20 % — so it trips instantaneously between roughly 28.8 A and 43.2 A. This is designed for loads with high inrush current, such as small motors, transformers, or solenoid valves, where a B or C curve would nuisance-trip on startup.

Does the A9F05203 include earth-leakage protection?

No. Earth-leakage protection requires a separate Vigi iC60 block. This MCB alone provides overcurrent and short-circuit protection only.