Skip to main content
Schneider Electric A9F05206 — 2-Pole MCB (DIN Rail)

Schneider Electric A9F05206 Acti9 iC60N MCB, 6 A, D Curve, 2

MPNA9F05206
Active

Schneider Electric Acti9 iC60N miniature circuit breaker, A9F05206, 6 A rated current, D curve, 2 poles, 36 mm width, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F05206 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameIC60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F05206 — Electrical
ParameterValue
Rated current [In]6 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC DC
Network frequency50/60 Hz
A9F05206 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F05206 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F05206 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F05206 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

Panel-fit and breaking capacity

The A9F05206 is a 2-pole, 6 A miniature circuit breaker from the Acti9 iC60N family, designed for DIN-rail mounting in distribution panels. Its 36 mm width (4 x 9 mm pitches) fits standard modular enclosures; the 78.5 mm depth and 91 mm height leave clearance for gland plates and cable ducts. Rated Icu at 220…240 V AC is 20 kA; at 380…415 V AC it holds 10 kA. Icn per EN/IEC 60898-1 is 6 kA at 400 V AC. For a 6 A device these margins cover most industrial distribution boards without cascading upstream. The D curve magnetic trip operates at 12 x In ±20 %, so it tolerates the inrush of small motors, transformers, or solenoid banks without nuisance tripping on start-up.

Dual-standard certification and lifecycle

Certified to both EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household / similar) — a dual rating that lets the same part serve control-panel distribution and branch-circuit protection under one BOM line. Lifecycle status is current production. Pollution degree 3 per IEC 60947-2 suits environments with conductive pollution or occasional condensation — typical for factory-floor panels not sealed to NEMA 4X.

Connection and wiring

The thermal-magnetic trip unit requires no external power — the breaker is self-powered for overcurrent sensing. IP20 finger-safe terminals are standard for enclosed distribution boards. A separate earth-leakage block (Vigi iC60) can be added on the downstream side for RCD protection without replacing the MCB.

Frequently asked questions

What is A9F05206's listed depth?

The depth is 78.5 mm, with a width of 36 mm and height of 91 mm — standard for a 2-pole iC60N on DIN rail.

What compliance documentation does Schneider provide for A9F05206?

The breaker carries dual certification to EN/IEC 60947-2 and EN/IEC 60898-1. Pollution degree 3, tropicalisation class 2, and IP20 are documented. RoHS and REACH declarations are standard Schneider documentation for the Acti9 range.

Where can I buy the A9F05206?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.