Schneider Electric A9F05216 — 2-Pole MCB (DIN Rail)

Schneider Electric A9F05216 Acti9 iC60N MCB, 16 A, D Curve,

MPNA9F05216
Active

Schneider Electric Acti9 iC60N, miniature circuit-breaker, 16 A, D curve, 2P, 36 mm, breaking capacity 36 kA Icu at 12-133 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F05216 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameIC60N
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F05216 — Electrical
ParameterValue
Rated current [In]16 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)DC AC
Network frequency50/60 Hz
A9F05216 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F05216 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F05216 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F05216 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F05216 is a 16 A, D-curve, 2-pole miniature circuit-breaker from the Acti9 iC60N series, built for distribution panels. It sits on a DIN rail, takes up 36 mm (4 x 9 mm pitches), and is rated for both AC and DC networks at 50/60 Hz. The D curve means its magnetic trip fires at 12 x In (±20%), so it handles high inrush currents typical of motor loads, transformers, or discharge lighting without nuisance tripping. For a 16 A breaker, that's around 192 A instantaneous trip threshold. Breaking capacity is the headline: 36 kA Icu at 12-133 V AC, 20 kA at 220-240 V, 10 kA at 380-415 V, and 6 kA at 440 V — all per IEC 60947-2. It also carries a 10 kA Icn at 400 V per IEC 60898-1.

The 36 mm width (2-pole) fits a typical 4-module slot in a consumer unit or distribution board. Terminals accept 1-25 mm² rigid or 1-16 mm² flexible, with a double-terminal design for daisy-chaining or ring-feed. Torque to 2 N·m, strip 14 mm.

Dual-certified to both IEC 60898-1 (the household/industrial MCB standard) and IEC 60947-2 (the industrial circuit-breaker standard). That dual rating gives it a wider acceptance for both residential and industrial specs. Also carries the isolation suitability mark per both standards — you can use it as a disconnector.

Frequently asked questions

What is the A9F05216's breaking capacity at 400 V?

At 380-415 V AC it carries 10 kA Icu (IEC 60947-2) and a 10 kA Icn at 400 V (IEC 60898-1). At 440 V the Icu drops to 6 kA.

MPN