A9F05232 is a Schneider Electric Acti9 iC60 miniature circuit breaker with a D trip curve, 32 A rated current, and 2 poles. It's a thermal-magnetic unit for AC/DC distribution networks, rated to isolate per EN/IEC 60898-1 and EN/IEC 60947-2. Breaking capacity is 36 kA Icu at 12…133 V AC, 20 kA at 220…240 V, and 10 kA at 380…415 V, with an Icn of 6 kA at 400 V per EN/IEC 60898-1. That's a lot of fault-clearing muscle for a 2-module (36 mm wide) package.
A9F05232 Acti9 iC60 D32 2P MCB, 32 A, 36 kA
Schneider Electric Acti9 iC60 miniature circuit breaker, type A9F05232, D curve, 32 A rated current, 2 poles, 36 kA Icu at 12-133 V AC, DIN-rail mount, thermal-magnetic trip.
Specifications
| Parameter | Value |
|---|---|
| Product name | Acti9 iC60 |
| Series / family | Acti9 |
| Device short name | IC60N |
| Product / component type | Miniature circuit-breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current [In] | 32 A |
| Number of protected poles | 2 |
| Pole configuration | 2P |
| Network type (AC/DC) | AC DC |
| Network frequency | 50/60 Hz |
| Parameter | Value |
|---|---|
| Tripping curve code | D |
| Magnetic tripping limit | 12 x In +/- 20 % |
| Breaking capacity (Icu) | 36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| Rated service breaking capacity [Ics] | 27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC |
| Energy limitation class | 3 conforming to EN/IEC 60898-1 |
| Suitable for isolation | Yes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2 |
| Overvoltage category | IV |
| Trip unit technology | Thermal-magnetic |
| Earth-leakage protection | Separate block |
| Operating / control type | Toggle |
| Mechanical durability (cycles) | 20000 cycles |
| Parameter | Value |
|---|---|
| 9 mm pitches | 4 |
| Width | 36 mm |
| Height | 91 mm |
| Depth | 78.5 mm |
| Mounting support | DIN rail |
| Terminal connections | Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible |
| Terminal tightening torque | 3.5 N.m top or bottom |
| Local signalling / indication | Trip indicator |
| Contact position indicator | Yes |
| Parameter | Value |
|---|---|
| Operating temperature range | -35...70 °C |
| Storage temperature range | -40...85 °C |
| Relative humidity | 95 % at 55 °C |
| Parameter | Value |
|---|---|
| Standards / compliance | EN/IEC 60947-2 EN/IEC 60898-1 |
Product details
Frequently asked questions
What is A9F05232's depth?
78.5 mm. That's the body depth, not including the toggle handle throw.
What standards does A9F05232 comply with?
Dual-rated to EN/IEC 60947-2 and EN/IEC 60898-1. That means it's certified for both industrial (60947-2) and residential/commercial (60898-1) applications — useful for a panel that needs to meet both a local code and a machine directive.
Where can I buy A9F05232 and how do I get a price?
Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for this order code.