Schneider Electric A9F05302 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F05302 Acti9 iC60N MCB, 2 A, D Curve, 3

MPNA9F05302
Active

Schneider Electric Acti9 iC60N, A9F05302, miniature circuit breaker, 3P, 2 A, D curve, 50 kA Icu at 415 V AC, DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F05302 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F05302 — Ratings
ParameterValue
Rated current (In)2 A
Poles configuration3P
Number of protected poles3
Breaking capacity50 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)50 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 25 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F05302 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F05302 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F05302 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F05302 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F05302 is an Acti9 iC60N miniature circuit breaker, 3-pole, rated 2 A with a D tripping curve. It carries a 50 kA Icu breaking capacity at 415 V AC per EN/IEC 60947-2 and 6 kA Icn at 400 V per EN/IEC 60898-1 — the dual standard rating means it qualifies for both industrial (60947-2) and domestic/commercial (60898-1) installations, so you can spec it into a distribution board or an industrial panel without changing the part number. At 2 A, this is a control-circuit or instrumentation feeder breaker, not a main distribution device.

At 440 V it drops to 25 kA Icu, and at 600 V (if applicable) it falls further; the 6 kA Icn at 400 V under 60898-1 is the lower service rating for domestic-style coordination. For industrial panels, the 60947-2 figures govern, and the 50 kA at 415 V means you can place this downstream of a transformer rated up to about 2 MVA and still maintain selectivity with a larger upstream device.

Snap-on DIN rail mount, 6 x 9 mm pitches wide (54 mm). Double terminals top and bottom accept up to 25 mm² rigid or 16 mm² flexible — plenty for a 2 A circuit where you'd typically run 1.5 or 2.5 mm². IP20 finger-safe front; the trip indicator shows clear local signalling.

Frequently asked questions

What is the breaking capacity of A9F05302 at 415 V?

50 kA Icu at 380…415 V AC per EN/IEC 60947-2, and 6 kA Icn at 400 V per EN/IEC 60898-1.

What does the D curve mean on this 2 A breaker?

The D curve trips magnetically at 12 x In (24 A) ±20%, so it tolerates the high inrush of small transformers, solenoid banks, or motor starters without nuisance tripping.

Where can I buy A9F05302 and how is it quoted?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer.

What compliance documentation is available for A9F05302?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1. Tropicalisation class 2 per IEC 60068-1 is also listed. For specific RoHS, REACH, or UL documentation, the manufacturer's product compliance portal provides the declarations.

MPN
A9F05302