Schneider Electric A9F05320 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F05320 Acti9 iC60N MCB, D Curve, 20 A,

MPNA9F05320
Active

Schneider Electric Acti9 iC60N, miniature circuit breaker, A9F05320, 3P, 20 A, D curve, 36 kA Icu at 12-133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F05320 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F05320 — Ratings
ParameterValue
Rated current (In)20 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F05320 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F05320 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F05320 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F05320 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F05320 is a 3-pole Acti9 iC60N miniature circuit breaker rated 20 A with a D tripping curve. The 20 A rating and 3 poles make it a distribution-level breaker for a three-phase subfeed, not a final branch circuit for socket outlets. Breaking capacity is rated per two standards: 36 kA Icu at 12-133 V AC and 20 kA Icu at 220-240 V AC under EN/IEC 60947-2, plus 10 kA Icn at 400 V AC under EN/IEC 60898-1. The 60947-2 rating governs industrial panel SCCR; the 60898-1 rating applies when the breaker is used in a residential or commercial final-distribution board. For a 400 V industrial panel, the 10 kA Icu at 380-415 V AC is the number that determines whether this breaker coordinates with the upstream fault level. Thermal-magnetic trip technology with a separate earth-leakage block (Vigi iC60) means the breaker itself provides overcurrent and short-circuit protection; residual-current protection is added by clipping an RCD block onto the same DIN-rail footprint. The contact position indicator and trip indicator give local visual status — useful during panel commissioning when the door is open.

Snap-on DIN-rail mount (EN/IEC 60715), 54 mm wide (6 x 9 mm pitches). The 78.5 mm depth and 91 mm height fit standard distribution board enclosures. IP20 finger-safe front — suitable for enclosed panels, not for outdoor or washdown locations.

Frequently asked questions

What is the breaking capacity of A9F05320 at 400 V?

At 380-415 V AC the A9F05320 is rated 10 kA Icu under EN/IEC 60947-2, and 10 kA Icn at 400 V under EN/IEC 60898-1.

Where can I buy A9F05320 and how is it quoted?

The A9F05320 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What is the D curve magnetic trip threshold on this breaker?

The D curve trips magnetically at 12 x In ±20 %, meaning the 20 A breaker will trip instantaneously between approximately 192 A and 288 A.

MPN