Schneider Electric A9F05332 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F05332 Acti9 iC60N MCB, D Curve 32 A 3P

MPNA9F05332
Active

Schneider Electric Acti9 iC60N, miniature circuit-breaker, A9F05332, D curve, 32 A, 3P, 36 kA breaking capacity, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F05332 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F05332 — Ratings
ParameterValue
Rated current (In)32 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F05332 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F05332 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F05332 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F05332 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F05332 is an Acti9 iC60N miniature circuit-breaker (MCB) — a 3-pole, 32 A unit with a D tripping curve, designed for distribution boards and industrial control panels.

Breaking capacity — what it clears and where

Breaking capacity is the headline number for an MCB: the A9F05332 is rated 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V, all per EN/IEC 60947-2. It also carries a 10 kA Icn at 400 V per EN/IEC 60898-1. The 36 kA figure at low voltage is what you care about for high-fault utility feeds; the 10 kA at 400 V covers most European industrial distribution. Dual-certified to both the industrial (60947-2) and household (60898-1) standards, so it qualifies for either duty.

Height is 91 mm, depth 78.5 mm. The double terminals top and bottom accept 1–35 mm² rigid or 1–25 mm² flexible — enough for the 32 A feed and downstream tails. Tightening torque is 3.5 Nm; strip length 14 mm. IP20 finger-safe terminals, pollution degree 3, overvoltage category IV. That's a distribution-grade MCB ready for a main panel, not a branch-only device.

Frequently asked questions

What is the breaking capacity of the A9F05332?

36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V per EN/IEC 60947-2; also 10 kA Icn at 400 V per EN/IEC 60898-1.

What does the D curve mean on this MCB?

The D curve trips magnetically at 12 x In (12 x 32 A = 384 A) with a +/-20% tolerance, designed for loads with high inrush current like motors, transformers, and welding equipment.

What is the A9F05332's DIN-rail width?

It occupies 6 modules at 9 mm pitch, so 54 mm wide. Height is 91 mm, depth 78.5 mm.

Where can I buy the A9F05332 and what is the lead time?

Sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time estimate.

MPN
A9F05332