Schneider Electric A9F05363 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F05363 Acti9 iC60N MCB, 63 A, 3P, D Cur

MPNA9F05363
Active

Schneider Electric Acti9 iC60N, miniature circuit breaker, 63 A, 3P, D curve, 36 kA Icu breaking capacity, thermal-magnetic trip, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F05363 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F05363 — Ratings
ParameterValue
Rated current (In)63 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F05363 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F05363 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F05363 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F05363 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F05363 is an Acti9 iC60N miniature circuit breaker rated for 63 A on a 3-pole configuration with a D tripping curve. It carries a 36 kA Icu breaking capacity at 12–133 V AC, stepping down to 10 kA Icu at 380–415 V AC per EN/IEC 60947-2, and 10 kA Icn at 400 V AC per EN/IEC 60898-1.

At 400 V AC, the A9F05363 delivers 10 kA Icn under EN/IEC 60898-1 and 10 kA Icu under EN/IEC 60947-2. That Icu figure is the same at 380–415 V AC, so the part holds its interrupting rating across the common European low-voltage distribution band. For a panel builder coordinating downstream MCBs with an upstream molded-case or air circuit breaker, that 10 kA at 400 V gives a solid selectivity window — the iC60N will clear a fault before the upstream device sees it, provided the upstream breaker's instantaneous trip is set above 10 kA.

The A9F05363 carries a current lifecycle status from Schneider Electric. It is an active catalog item within the Acti9 range, which means it remains a standard BOM line for new panel designs and replacement spares.

IP20 rated, so it lives inside an enclosure — no washdown exposure. The toggle actuator and trip indicator provide local visual status, and the contact position indicator confirms isolation suitability per both EN/IEC 60898-1 and 60947-2.

Frequently asked questions

Where can I buy the A9F05363?

The A9F05363 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the A9F05363 at 400 V AC?

At 400 V AC, the A9F05363 delivers 10 kA Icn per EN/IEC 60898-1 and 10 kA Icu per EN/IEC 60947-2.

What does the D curve on the A9F05363 mean?

The D curve means the magnetic trip threshold is 12 x In ±20%, so the breaker will hold through the high inrush currents typical of motor starting, small transformers, or discharge lighting without nuisance tripping.

What standards does the A9F05363 comply with?

The A9F05363 is certified to EN/IEC 60947-2 and EN/IEC 60898-1, covering both industrial and residential installation applications.