The Schneider Electric A9F06113 is an Acti9 iC60H miniature circuit breaker — a 1-pole, 13 A thermal-magnetic MCB with a B-curve trip characteristic.
Breaking capacity and what it means for your panel
The A9F06113 carries a 42 kA Icu at 12-60 VAC (50/60 Hz) per EN/IEC 60947-2, and 30 kA at 100-133 VAC, 15 kA at 220-240 VAC. On DC circuits it delivers 20 kA Icu at 12-60 VDC and 15 kA at 60-72 VDC. The Icn rating under EN/IEC 60898-1 is 10,000 A at 230 VAC.
Snap-on DIN rail mounting (per) — 18 mm per pole width, 91 mm height, 78.5 mm depth. Two 9 mm pitches occupied. Double terminals top and bottom accept 1-25 mm² rigid or 1-16 mm² flexible copper. Tightening torque 2 N·m. IP20 finger-safe terminals; pollution degree 3 rated for the industrial environment inside the enclosure.