Schneider Electric A9F06150

A9F06150 Acti9 iC60H MCB, 1P B-curve 50 A, 10 kA IEC 60898-1

MPN A9F06150
Obsolete

Schneider Electric Acti9 iC60H, miniature circuit breaker, 1P, B-curve, 50 A, 10 kA Icn at 230 V AC, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F06150 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C
Storage temperature-40...85 °C

All specifications

A9F06150 additional specifications
ParameterValue
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width18 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

What this MCB carries — and what it clears

The A9F06150 is a 1-pole Acti9 iC60H miniature circuit breaker rated 50 A with a B-curve magnetic trip at 4 x In ±20 %. It is listed to both EN/IEC 60947-2 (Category A) and EN/IEC 60898-1, so it can serve distribution panels under either standard — the 60947-2 rating gives the higher short-circuit capacity numbers for industrial coordination studies. Breaking capacity reaches 42 kA Icu at 12–60 V AC, 15 kA Icu at 220–240 V AC, and 10 000 A Icn at 230 V AC under the household standard. The 78.5 mm depth and 18 mm width (2 x 9 mm pitches) fit a standard DIN-rail enclosure; double terminals top and bottom accept up to 35 mm² rigid or 25 mm² flexible.

The 18 mm width occupies two 9 mm module pitches — one pole, one unit. Double terminals top and bottom allow through-wiring or daisy-chaining without extra links. Wire stripping length is 14 mm; tightening torque 3.5 N.m. IP20 finger-safe protection applies once installed in an enclosure.

Standards and approvals — what they certify

Dual-rated to EN/IEC 60898-1 (the household standard for MCBs) and EN/IEC 60947-2 (the industrial standard for circuit breakers). The 60947-2 listing gives the higher Icu breaking capacities needed for industrial coordination studies; the 60898-1 listing gives the Icn rating for residential or commercial distribution. Overvoltage category IV (equipment at the origin of the installation, e.g. main panel). Suitability for isolation is confirmed under both standards, meaning the breaker can be used as a disconnecting means when visibly open.

MPN