Skip to main content
Schneider Electric A9F06306 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F06306 Acti9 iC60H MCB, 6 A, 3P, Curve

MPNA9F06306
Active

Schneider Electric Acti9 iC60H, miniature circuit-breaker, 6 A, 3P, curve B, 42 kA Icu at 12-133 V AC, DIN rail mount, white.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F06306 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F06306 — Ratings
ParameterValue
Rated current (In)6 A
Poles configuration3P
Number of protected poles3
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F06306 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F06306 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F06306 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F06306 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F06306 is an Acti9 iC60H miniature circuit-breaker rated 6 A, three-pole, curve B, with a breaking capacity of 42 kA Icu at 12...133 V AC and 30 kA Icu at 220...240 V AC (50/60 Hz) per EN/IEC 60947-2. Mounts on a DIN rail (6 x 9 mm pitches), 54 mm wide, 91 mm tall, 78.5 mm deep. The thermal-magnetic trip unit is sealed; no user adjustment. A separate earth-leakage block (Vigi iC60) can be added downstream for RCD protection if needed.

Compliance and approvals

Rated insulation voltage 500 V AC, overvoltage category IV, pollution degree 3. Suitability for isolation is confirmed under both standards. IP20 finger-safe terminals. The white housing and toggle actuator with trip indicator give a clear visual on the panel.

Frequently asked questions

How do I get current pricing and availability for the A9F06306?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity of the A9F06306?

The A9F06306 carries 42 kA Icu at 12...133 V AC, 30 kA Icu at 220...240 V AC, and 15 kA Icu at 380...415 V AC (50/60 Hz) per EN/IEC 60947-2, plus 15 kA Icn at 400 V AC per EN/IEC 60898-1.

What compliance documentation does Schneider provide for the A9F06306?

The MCB is certified to EN/IEC 60947-2 and EN/IEC 60898-1. It carries a rated insulation voltage of 500 V AC, overvoltage category IV, pollution degree 3, and tropicalisation class 2 per IEC 60068-1. IP20 finger-safe protection is confirmed per IEC 60529.

MPN