Skip to main content
Schneider Electric A9F06332 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F06332 Acti9 iC60H MCB, 32 A, 3P, B Cur

MPNA9F06332
Active

Schneider Electric Acti9 iC60H, A9F06332, 3P miniature circuit breaker, 32 A, B curve, 42 kA Icu at 12–133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F06332 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F06332 — Ratings
ParameterValue
Rated current (In)32 A
Poles configuration3P
Number of protected poles3
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F06332 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F06332 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F06332 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F06332 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F06332 is a Schneider Electric Acti9 iC60H miniature circuit breaker — 32 A rated current, 3-pole, B-curve trip characteristic. The 42 kA Icu at 12–133 V AC is the maximum short-circuit current it can interrupt without damage at those voltages; at 400 V AC the Icn is 15 kA per EN/IEC 60898-1, which is the standard domestic/commercial breaking capacity. That 15 kA at 400 V tells you it's rated for distribution boards with moderate fault levels — not for high-fault industrial mains. The thermal-magnetic trip unit covers both overload (thermal bimetal) and short-circuit (magnetic coil). It's certified to both EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household), so it can be specified in either context. The 3-pole configuration (3P) switches all three phases simultaneously, which is standard for three-phase distribution. DIN-rail mounting (snap-on) means it clips directly onto the standard 35 mm rail in any distribution board or sub-panel.

Dimensions: 91 mm high, 54 mm wide, 78.5 mm deep. The 54 mm width (3 x 18 mm per pole) is standard for a 3P MCB on DIN rail — it occupies 6 x 9 mm pitches. The toggle control and trip indicator give visual status without needing to open the panel door.

Frequently asked questions

Who supplies A9F06332 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

What is A9F06332's breaking capacity at 400 V?

At 400 V AC 50/60 Hz, the Icn is 15 kA per EN/IEC 60898-1. The Icu per EN/IEC 60947-2 is 15 kA at 380–415 V AC and 10 kA at 440 V AC.

What compliance standards does A9F06332 meet?

It is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with tropicalisation class 2 per IEC 60068-1. Suitability for isolation is confirmed under both standards.

MPN
A9F06332