Skip to main content
Schneider Electric A9F06340 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F06340 Acti9 iC60H MCB, 40 A, 3P, B Cur

MPNA9F06340
Active

Schneider Electric Acti9 iC60H, miniature circuit breaker, 40 A, 3P, B curve, 42 kA Icu at 12-133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F06340 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F06340 — Ratings
ParameterValue
Rated current (In)40 A
Poles configuration3P
Number of protected poles3
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F06340 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F06340 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F06340 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F06340 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F06340 is a 40 A, 3-pole miniature circuit breaker from the Acti9 iC60H series, with a B-curve magnetic trip characteristic. Rated breaking capacity reaches 42 kA Icu at 12-133 V AC (EN/IEC 60947-2), stepping down to 30 kA at 220-240 V AC, 15 kA at 380-415 V AC, and 10 kA at 440 V AC. Under EN/IEC 60898-1 it is rated 15 kA Icn at 400 V AC. That dual-standard rating means this breaker can serve both industrial (60947-2) and residential/commercial (60898-1) installations, but the 60947-2 figures govern for industrial panel builds where fault current may exceed 10 kA. The B curve trips magnetically at 4 x In (±20 %), so for a 40 A breaker the magnetic release engages between 128 A and 192 A. This suits cable protection in circuits with low inrush — lighting, resistive loads, or long distribution runs where you want fast clearing on short-circuit but tolerance for moderate startup peaks.

Snap-on DIN rail mounting, 54 mm wide (6 x 9 mm pitches). The 78.5 mm depth and 91 mm height fit standard distribution board cutouts. Overvoltage category IV covers the main distribution board entry point. IP20 finger-safe terminals. Earth-leakage protection requires a separate block (Vigi iC60) — the MCB itself does not include RCD functionality.

Frequently asked questions

What is the breaking capacity of A9F06340 at 400 V?

Under EN/IEC 60898-1 it is rated 15 kA Icn at 400 V AC. Under EN/IEC 60947-2 the Icu is 15 kA at 380-415 V AC and 10 kA at 440 V AC.

What is the closest alternative to A9F06340 in the Acti9 family?

Within the Acti9 iC60 range, the C-curve variant (A9F06340C) shares the same 40 A, 3P, DIN-rail footprint and breaking capacity. The difference is the magnetic trip threshold: C curve trips at 5-10 x In versus B curve at 3-5 x In. Choose B for resistive/lighting loads, C for moderate motor or transformer inrush.

Where can I buy A9F06340?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN
A9F06340