Skip to main content
Schneider Electric A9F06350 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F06350 Acti9 iC60H MCB, 50 A, 3P, B-Cur

MPNA9F06350
Active

Schneider Electric Acti9 iC60H, A9F06350, miniature circuit breaker, 3P, 50 A, B-curve, 42 kA breaking capacity at 12-133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F06350 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F06350 — Ratings
ParameterValue
Rated current (In)50 A
Poles configuration3P
Number of protected poles3
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F06350 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F06350 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F06350 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F06350 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F06350 is a 3-pole Acti9 iC60H miniature circuit breaker rated at 50 A with a B-curve trip characteristic. It protects branch circuits in distribution panels against overloads and short circuits, using a thermal-magnetic trip unit that responds to sustained overcurrents thermally and to instantaneous faults magnetically. Depth is 78.5 mm, which matters for enclosure depth planning when gland plates or busbar shrouds are tight. IP20 finger protection is standard for panel-internal use; no washdown rating here, so keep it behind the enclosure door.

This breaker carries a 42 kA Icu at 12-133 V AC — that's its ultimate short-circuit breaking capacity at the low-voltage end, typical for control transformer secondaries or 48 VAC circuits. At 220-240 V AC it's 30 kA Icu, and at 380-415 V AC it's 15 kA Icu. The takeaway: if your service entrance fault current exceeds 10 kA at 400 V, this breaker still clears it at its Icu rating, but it may not be reusable afterward — that's the difference between Icn (service continuity expected) and Icu (one-shot survival).

Standards and compliance — what the approvals certify

This MCB is certified to both EN/IEC 60947-2 (industrial application, category A — no intentional short-time delay) and EN/IEC 60898-1 (household and similar installation). Dual certification means it's accepted in both industrial control panels and commercial distribution boards across Europe and many other jurisdictions that adopt IEC standards. Overvoltage category IV confirms it's suitable for installation at the origin of the installation, before any step-down transformer.

Frequently asked questions

What is the breaking capacity of A9F06350 at 400 V?

At 400 V AC the A9F06350 has an Icn of 10 kA per EN/IEC 60898-1 and an Icu of 15 kA at 380-415 V AC per EN/IEC 60947-2. The 10 kA Icn is the rating for service continuity; the 15 kA Icu is the ultimate one-shot capacity.

Where can I buy A9F06350 and how is it quoted?

The A9F06350 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume and delivery schedule.

What is the depth of A9F06350 for enclosure planning?

The depth is 78.5 mm. With 54 mm width occupying 6 module pitches on DIN rail, it fits standard distribution board cutouts. Allow clearance for busbar connections and the toggle handle arc.

What compliance documentation does A9F06350 carry?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with pollution degree 3, overvoltage category IV, and tropicalisation class 2 per IEC 60068-1. It is suitable for isolation per both standards.

MPN
A9F06350