Skip to main content
Schneider Electric A9F06413 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F06413 Acti9 iC60H MCB, 13 A, 4P, B-Cur

MPNA9F06413
Active

Schneider Electric Acti9 iC60H, A9F06413, miniature circuit breaker, 4P, 13 A, B-curve, 42 kA Icu at 12-133 V AC, DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F06413 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F06413 — Ratings
ParameterValue
Rated current (In)13 A
Poles configuration4P
Number of protected poles4
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F06413 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F06413 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F06413 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F06413 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F06413 is a Schneider Electric Acti9 iC60H miniature circuit breaker rated 13 A with a B-curve trip characteristic, meaning magnetic tripping occurs at 4 x In ±20 %. The 4-pole (4P) configuration breaks all live conductors. Breaking capacity is 42 kA Icu at 12-133 V AC, 30 kA at 220-240 V AC, and 15 kA at 380-415 V AC per EN/IEC 60947-2. Under EN/IEC 60898-1 it carries 15 kA Icn at 400 V AC. The thermal-magnetic trip unit combines a bimetal for overload protection and a solenoid for short-circuit. The IP20 finger-safe terminals accept rigid cable up to 25 mm² or flexible up to 16 mm², with a wire-stripping length of 14 mm and tightening torque of 2 N.m.

Deployment context

The toggle handle and trip indicator give local status without opening the door. The white housing is standard for the Acti9 range, which is often used in commercial building distribution and light-industrial sub-distribution boards across Europe and markets that follow IEC standards.

Frequently asked questions

What is the breaking capacity of A9F06413?

42 kA Icu at 12-133 V AC, 30 kA at 220-240 V AC, 15 kA at 380-415 V AC per EN/IEC 60947-2, and 15 kA Icn at 400 V AC per EN/IEC 60898-1.

What standards does A9F06413 comply with?

Dual-certified to EN/IEC 60947-2 (industrial MCB standard) and EN/IEC 60898-1 (domestic MCB standard). Also carries suitability for isolation per both standards, pollution degree 3, and overvoltage category IV.

MPN
A9F06413