Skip to main content
Schneider Electric A9F06450 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F06450 Acti9 iC60H MCB, B-Curve 50A 4P

MPNA9F06450
Active

Schneider Electric Acti9 iC60H miniature circuit breaker, B-curve, 50 A rated, 4-pole, 42 kA Icu breaking capacity at 12-133 V AC, DIN rail mount, white.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F06450 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F06450 — Ratings
ParameterValue
Rated current (In)50 A
Poles configuration4P
Number of protected poles4
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F06450 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F06450 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F06450 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F06450 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F06450 is a 4-pole Acti9 iC60H miniature circuit breaker rated 50 A with a B-curve trip characteristic. The 42 kA Icu at 12-133 V AC and 30 kA Icu at 220-240 V AC (EN/IEC 60947-2) give it high fault-clearing capacity for industrial panel applications; at 380-415 V AC it still interrupts 15 kA. That SCCR headroom lets you coordinate downstream without cascading failure.

Standards and deployment

Rated to both EN/IEC 60898-1 (domestic MCB standard) and EN/IEC 60947-2 (industrial circuit-breaker standard), so it qualifies for distribution boards and industrial panel feeders alike. Mounts on standard DIN rail; width is 72 mm (8 x 9 mm pitches), depth 78.5 mm, height 91 mm — fits a standard 4-pole MCB slot in any Acti9 distribution board.

Current-production part. The Acti9 iC60 series is Schneider's standard panel MCB line, widely specified for commercial and light-industrial distribution.

Frequently asked questions

What is the breaking capacity of A9F06450?

42 kA Icu at 12-133 V AC, 30 kA Icu at 220-240 V AC, 15 kA Icu at 380-415 V AC, and 10 kA Icu at 440 V AC per EN/IEC 60947-2; also rated 10 kA Icn at 400 V AC per EN/IEC 60898-1.

What standards does A9F06450 comply with?

Certified to EN/IEC 60947-2 and EN/IEC 60898-1, with suitability for isolation confirmed under both standards.

MPN
A9F06450