Schneider Electric A9F06610 — 1-Pole MCB (DIN Rail)

A9F06610 Acti9 iC60H MCB, B Curve 10 A, 1P+N, 42 kA

MPNA9F06610
Active

Schneider Electric Acti9 iC60H miniature circuit breaker, A9F06610, B curve, 10 A, 1P+N, 42 kA Icu at 12-60 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F06610 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC60H
Poles description1P + N
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F06610 — Electrical & Protection
ParameterValue
Rated current (In)10 A
Tripping curve codeB
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity (Icu / AIR)42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F06610 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width36 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom

Environmental

A9F06610 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F06610 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F06610 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F06610 is an Acti9 iC60H miniature circuit breaker with a B curve, rated 10 A, 1P+N, and a breaking capacity of 42 kA Icu at 12-60 V AC. The thermal-magnetic trip unit provides overcurrent and short-circuit protection, with magnetic tripping at 4 x In +/- 20 %.

The B curve (magnetic trip at 4 x In) means this MCB is suited for resistive or general-purpose loads with low inrush — common in lighting, socket circuits, and control transformers. The 10 A rating handles branch circuits up to that continuous current. The 42 kA Icu at 12-60 V AC is the ultimate breaking capacity under EN/IEC 60947-2; at 230 V AC the Icn under EN/IEC 60898-1 is 10000 A. The 1P+N configuration switches the phase and provides a switched neutral, with the neutral on the left side.

Frequently asked questions

What is the breaking capacity of A9F06610?

The breaking capacity is 42 kA Icu at 12-60 V AC (EN/IEC 60947-2), 30 kA Icu at 100-133 V AC, 15 kA Icu at 220-240 V AC, and 10000 A Icn at 230 V AC (EN/IEC 60898-1).

What standards does A9F06610 comply with?

It complies with EN/IEC 60947-2 and EN/IEC 60898-1, and is suitable for isolation per both standards. Pollution degree 3, overvoltage category IV.

Where can I buy A9F06610?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN