Skip to main content
Schneider Electric A9F06632 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F06632 Acti9 iC60H MCB, 32A B-Curve 1P+

MPNA9F06632
Active

Schneider Electric Acti9 iC60H, A9F06632, miniature circuit breaker, 32 A, B-curve, 1P+N, 15 kA Icu at 240 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F06632 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC60H
Poles description1P + N
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F06632 — Electrical & Protection
ParameterValue
Rated current (In)32 A
Tripping curve codeB
Magnetic tripping limit4 x In +/- 20 %
Breaking capacity (Icu / AIR)42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F06632 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Mounting supportDIN rail
Width36 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)3.5 N.m top or bottom

Environmental

A9F06632 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F06632 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F06632 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F06632 is an Acti9 iC60H miniature circuit breaker rated 32 A with a B-curve trip characteristic, 1P+N configuration, and a 15 kA Icu breaking capacity at 220–240 V AC per EN/IEC 60947-2.

The iC60H designation means this breaker's industrial breaking capacity (Icu) is 15 kA at 220–240 V AC, 30 kA at 100–133 V AC, and 42 kA at 12–60 V AC. Under the domestic standard (60898-1) its Icn is 10 kA at 230 V AC. For a 32 A circuit, 15 kA Icu gives solid selectivity headroom upstream of a typical 25 kA or 36 kA main breaker in a distribution board — the fault energy is unlikely to exceed the breaker's interrupt rating before the upstream device clears. The utilisation category is A (no intentional time delay for selectivity), so coordination relies on the upstream device's delay curve, not this breaker's.

Snap-on DIN rail mount per EN/IEC 60715. Neutral is on the left, switched pole on the right. Terminals accept double conductors up to 35 mm² rigid or 25 mm² flexible; strip length is 14 mm, tightening torque 3.5 N·m.

Frequently asked questions

What compliance documentation does Schneider provide for A9F06632?

The breaker is dual certified to EN/IEC 60947-2 and EN/IEC 60898-1, carries IP20 per IEC 60529, and is tropicalised to class 2 per IEC 60068-1. Documentation including the declaration of performance and CE declaration is available from Schneider Electric's product documentation portal.

MPN