The Schneider Electric A9F06632 is an Acti9 iC60H miniature circuit breaker rated 32 A with a B-curve trip characteristic, 1P+N configuration, and a 15 kA Icu breaking capacity at 220–240 V AC per EN/IEC 60947-2.
The iC60H designation means this breaker's industrial breaking capacity (Icu) is 15 kA at 220–240 V AC, 30 kA at 100–133 V AC, and 42 kA at 12–60 V AC. Under the domestic standard (60898-1) its Icn is 10 kA at 230 V AC. For a 32 A circuit, 15 kA Icu gives solid selectivity headroom upstream of a typical 25 kA or 36 kA main breaker in a distribution board — the fault energy is unlikely to exceed the breaker's interrupt rating before the upstream device clears. The utilisation category is A (no intentional time delay for selectivity), so coordination relies on the upstream device's delay curve, not this breaker's.
Snap-on DIN rail mount per EN/IEC 60715. Neutral is on the left, switched pole on the right. Terminals accept double conductors up to 35 mm² rigid or 25 mm² flexible; strip length is 14 mm, tightening torque 3.5 N·m.