Skip to main content
Schneider Electric A9F06640

Schneider Electric A9F06640 Acti9 iC60H MCB, 40A B-Curve 1P+

MPN A9F06640
Obsolete

Schneider Electric Acti9 iC60H, A9F06640, miniature circuit breaker, 40 A, B-curve, 1P+N, 10 kA Icn, DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F06640 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C

All specifications

A9F06640 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width36 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F06640 is an Acti9 iC60H miniature circuit breaker (MCB) rated at 40 A with a B-curve trip characteristic, 1P+N poles, and a breaking capacity of 10 kA Icn at 230 V AC per EN/IEC 60898-1.

The B-curve (4 x In magnetic trip limit, +/- 20%) means this MCB trips instantaneously at 4 times its 40 A rated current, i.e., between 128 A and 192 A. The 1P+N configuration switches the phase and provides a switched neutral, but only the phase pole is protected; the neutral pole is not overcurrent-protected. The left-side neutral position is fixed, so confirm busbar and wiring order before terminating.

This MCB is dual-certified to EN/IEC 60898-1 (domestic/similar installation standard, Icn rating) and EN/IEC 60947-2 (industrial standard, Icu rating). It is suitability for isolation per both standards, meaning it can be used as a disconnecting means under load. Overvoltage category IV means it can be installed at the origin of the installation (utility meter side), not just downstream sub-distribution.

Mounts on DIN rail and occupies 4 module pitches, each 9 mm, for a total width of 36 mm. Depth is 78.5 mm, height 91 mm. Terminals accept double conductors: 1...35 mm² rigid or 1...25 mm² flexible, with a tightening torque of 3.5 N.m and a wire strip length of 14 mm. IP20 finger-safe terminals suit enclosed panel installation but not washdown environments. The toggle control and trip indicator provide local status without opening the panel door.

MPN
A9F06640