Skip to main content
Schneider Electric A9F07140 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F07140 Acti9 iC60H MCB, 40 A, 1P, C-Cur

MPNA9F07140
Active

Schneider Electric Acti9 iC60H miniature circuit-breaker, 1P, 40 A, C-curve, 42 kA Icu at 12-60 V AC, dual-standard IEC 60947-2 / IEC 60898-1, 18 mm width.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07140 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC60H
Poles description1P
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F07140 — Electrical & Protection
ParameterValue
Rated current (In)40 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F07140 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)3.5 N.m top or bottom

Environmental

A9F07140 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F07140 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F07140 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The Schneider Electric A9F07140 is a 40 A, 1-pole miniature circuit-breaker from the Acti9 iC60H series, designed for distribution boards and sub-distribution panels. Rated for both AC and DC networks (50/60 Hz), this MCB carries a dual-standard certification: EN/IEC 60947-2 for industrial circuit-breaker performance and EN/IEC 60898-1 for household-type protection. That means it qualifies as a circuit-breaker for isolation (suitability for isolation marked on the device) and meets pollution degree 3, overvoltage category IV — suitable for main incoming panels, not just final subcircuits.

The headline breaking capacity is 42 kA Icu at 12-60 V AC (EN/IEC 60947-2). At 220-240 V AC it drops to 15 kA Icu, and at 230 V AC the Icn per IEC 60898-1 is 10,000 A. For DC applications, it offers 20 kA Icu at 12-60 V DC and 15 kA Icu at 60-72 V DC. For 230/400 V distribution, the 10 kA Icn is standard for final circuits; the 15 kA Icu gives headroom if you need to coordinate with a higher-rated upstream device.

Snaps onto a DIN rail (mounting support: DIN rail). Width is 18 mm (2 x 9 mm pitches), so it occupies one standard module position. Height 91 mm, depth 78.5 mm — fits standard distribution enclosures with 80-100 mm gutter depth. Terminals accept 1-35 mm² rigid or 1-25 mm² flexible conductors on double terminals (top and bottom). Tightening torque 3.5 N.m. Wire stripping length 14 mm. IP20 finger-safe protection on the front face.

Durability and environmental ratings

Rated for 10,000 electrical cycles and 20,000 mechanical cycles. Colour: white (standard for Acti9 residential/commercial range).

Frequently asked questions

Where can I buy A9F07140 and how do I get a price?

The A9F07140 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is A9F07140's listed depth (78.5 mm) on this component line?

The A9F07140 has a depth of 78.5 mm, which fits standard distribution enclosures with 80-100 mm gutter depth.

What is A9F07140's listed range (Acti9) on this component line?

The A9F07140 belongs to the Acti9 range, Schneider Electric's modular DIN-rail miniature circuit-breaker platform for residential, commercial, and light-industrial distribution.

MPN
A9F07140