The C-curve (magnetic tripping at 8 x In ±20 %) means it handles moderate inrush — typical for lighting, socket circuits, and small motor loads — without nuisance trips. The 42 kA Icu at 12-133 V AC (EN/IEC 60947-2) is the maximum fault current it can safely interrupt; at 380-415 V AC that drops to 15 kA Icu, and under the domestic standard (EN/IEC 60898-1) the Icn is 10 kA at 400 V AC. For a distribution board feeding mixed loads, this breaker covers both the higher SCCR needed at low voltage and the standard 10 kA domestic rating.
Deployment context