Schneider Electric Acti9 iC60H miniature circuit breaker, A9F07250, 50 A rated current, 2 poles, C-curve, 42 kA Icu breaking capacity at 133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07250 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameiC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution

Electrical

A9F07250 — Electrical
ParameterValue
Rated current [In]50 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC DC
Network frequency50/60 Hz

Protection

A9F07250 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu)42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07250 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes

Environmental

A9F07250 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C

Approvals

A9F07250 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

Schneider Electric A9F07250 is an Acti9 iC60H miniature circuit breaker — 50 A rated current, 2 poles, C-curve, thermal-magnetic trip unit. It sits on a DIN rail, occupies 4 modular pitches (36 mm width), and is rated for both AC and DC networks at 50/60 Hz. Overvoltage category IV means it's designed for the main incoming supply — not just sub-distribution.

The iC60H (the 'H' denotes high breaking capacity) delivers 42 kA Icu at 12…133 V AC, 30 kA at 220…240 V, 15 kA at 380…415 V, and 10 kA at 440 V per EN/IEC 60947-2. Under the domestic-standard EN/IEC 60898-1 it's rated 15 kA Icn at 400 V. That spread means you can coordinate downstream with lower-rated MCBs in a tiered panel — the iC60H clears faults fast enough that a 10 kA rated branch breaker won't see energy beyond its rating.

IP20 finger-safe front, but the busbar area is live when installed — standard panel practice. Pollution degree 3 and tropicalisation class 2 (IEC 60068-1) mean it handles condensation and conductive dust in unsealed enclosures.

Frequently asked questions

What is A9F07250's breaking capacity at 240 V?

30 kA Icu at 220…240 V AC per EN/IEC 60947-2.