The A9F07332 is a 32 A, 3-pole miniature circuit breaker from the Acti9 iC60H series, thermal-magnetic trip, C-curve (magnetic trip at 8 x In ±20 %). Rated breaking capacity hits 42 kA Icu at 12-133 V AC and 30 kA at 220-240 V AC (EN/IEC 60947-2); at 400 V the Icn is 10 kA (EN/IEC 60898-1). Mounts on DIN rail (54 mm width, 6 x 9 mm pitches), IP20 finger-safe terminals. Double terminals accept 1-35 mm² rigid or 1-25 mm² flexible — enough for 32 A feeder circuits with standard panel wiring.
Schneider Electric A9F07332 Acti9 iC60H MCB, 32 A, 3P, C-Cur
Schneider Electric Acti9 iC60H, A9F07332, miniature circuit breaker, 32 A, 3P, C-curve, breaking capacity 42 kA Icu at 12-133 V AC, 30 kA at 220-240 V AC, 15 kA at 380-415 V AC, 10 kA at 440 V AC, DIN-rail mount.
Specifications
Identification
| Parameter | Value |
|---|---|
| Product name | Acti9 iC60 |
| Product range | Acti9 |
| Product/component type | Miniature circuit-breaker |
| Device application | Distribution |
Ratings
| Parameter | Value |
|---|---|
| Rated current (In) | 32 A |
| Poles configuration | 3P |
| Number of protected poles | 3 |
| Breaking capacity | 42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| Rated service breaking capacity (Ics) | 21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC |
| Rated insulation voltage (Ui) | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Rated impulse withstand voltage (Uimp) | 6 kV conforming to EN/IEC 60947-2 |
| Network type (AC/DC) | DC AC |
| Network frequency | 50/60 Hz |
| Utilisation category | Category A conforming to EN/IEC 60947-2 |
| Overvoltage category | IV |
Protection
| Parameter | Value |
|---|---|
| Curve code | C |
| Trip unit technology | Thermal-magnetic |
| Magnetic tripping limit | 8 x In +/- 20 % |
| Earth-leakage protection | Separate block |
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1 |
| Limitation class | 3 conforming to EN/IEC 60898-1 |
| Electrical durability (cycles) | 10000 cycles |
| Mechanical durability (cycles) | 20000 cycles |
Mechanical
| Parameter | Value |
|---|---|
| Mounting support | DIN rail |
| Control type | Toggle |
| Terminal connection type | Double terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible |
| Terminal tightening torque | 3.5 N.m top or bottom |
| Wire stripping length | 14 mm for top or bottom connection |
| Contact position indicator | Yes |
| Local signalling/indication | Trip indicator |
| Width | 54 mm |
| Height | 91 mm |
| Depth | 78.5 mm |
| Number of 9 mm pitches | 6 |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | -35...70 °C |
| Storage ambient temperature | -40...85 °C |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Pollution degree | 3 conforming to EN/IEC 60947-2 |
| Relative humidity | 95 % at 55 °C |
| Tropicalisation class | 2 conforming to IEC 60068-1 |
Approvals
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-2 EN/IEC 60898-1 |
Product details
Frequently asked questions
How do I get current pricing and availability for A9F07332?
Sourced to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.
What is A9F07332's listed depth?
Depth is 78.5 mm.
What range does A9F07332 belong to?
The Acti9 range — specifically the iC60H device short name.
What compliance documentation does this brand provide for A9F07332?
Certified to EN/IEC 60947-2 and EN/IEC 60898-1. Pollution degree 3 per 60947-2; tropicalisation class 2 per IEC 60068-1. Separate earth-leakage protection block available.