Skip to main content
Schneider Electric A9F07340 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F07340 Acti9 iC60H MCB, 40 A, 3P, C-Cur

MPNA9F07340
Active

Schneider Electric Acti9 iC60H, A9F07340, miniature circuit breaker, 40 A, 3-pole, C-curve, 42 kA breaking capacity, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07340 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F07340 — Ratings
ParameterValue
Rated current (In)40 A
Poles configuration3P
Number of protected poles3
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F07340 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07340 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches6

Environmental

A9F07340 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F07340 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F07340 is an Acti9 iC60H miniature circuit breaker rated at 40 A, 3-pole, with a C-curve trip characteristic. It's a thermal-magnetic MCB built for distribution boards and sub-panels where you need overcurrent and short-circuit protection on a 3-phase load. Breaking capacity hits 42 kA Icu at 12–133 V AC, 30 kA at 220–240 V, and 15 kA at 380–415 V. That's a lot of fault-clearing muscle for a 40 A MCB — it'll ride through a hard short on a heavily-rated industrial panel without welding its contacts shut.

DIN rail fit and panel space

Snaps onto a standard DIN rail; width is 54 mm (6 x 9 mm pitches), height 91 mm, depth 78.5 mm. That 78.5 mm depth means it clears most shallow enclosures — check your gland plate clearance if you're retrofitting into a tight 100 mm-deep box.

Dual-rated to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (household/residential). That means it's accepted in both panel-building and final-distribution applications — a single part number covers both standards. Overvoltage category IV, so it can sit at the service entrance or main distribution board. Isolation suitable per both standards, with a visible contact position indicator and a trip indicator for quick fault identification. IP20 finger-safe terminals.

Frequently asked questions

What is A9F07340's listed depth?

78.5 mm — that's the dimension from the DIN rail mounting surface to the front of the breaker body.

What breaking capacity does A9F07340 have at 400 V?

15 kA Icu at 380–415 V AC per EN/IEC 60947-2, and 10 kA Icn at 400 V per EN/IEC 60898-1.

What compliance documentation does this brand provide for A9F07340?

The part is certified to EN/IEC 60947-2 and EN/IEC 60898-1. Standard Schneider Electric declarations of conformity cover these standards; specific RoHS/REACH documentation is available through the manufacturer's compliance portal.

MPN
A9F07340