Skip to main content
Schneider Electric A9F07401 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F07401 Acti9 iC60H MCB, 1 A C-Curve 4P,

MPNA9F07401
Active

Schneider Electric Acti9 iC60H, miniature circuit-breaker, 4P, 1 A, C-curve, 70 kA Icu at 415 V AC, DIN-rail mount, IP20.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07401 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F07401 — Ratings
ParameterValue
Rated current (In)1 A
Poles configuration4P
Number of protected poles4
Breaking capacity70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)70 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F07401 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07401 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F07401 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F07401 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F07401 is an Acti9 iC60H miniature circuit-breaker (MCB) rated at 1 A with a C-curve, 4 poles, and a breaking capacity of 70 kA Icu at 415 V AC. The C-curve (magnetic trip at 8 x In +/- 20%) means it tolerates moderate inrush, making it a standard choice for general distribution and mixed resistive-inductive loads like contactor coils and small motor circuits.

The 4-pole body occupies 8 x 9 mm pitches (72 mm wide), so it fits a standard 4-module slot in a distribution board. Height is 91 mm, depth 78.5 mm — check your enclosure depth if using a shallow gland plate or a compact consumer unit. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible on double terminals top and bottom; tightening torque is 2 N·m. The IP20 finger-safe front is standard for enclosed panels; no washdown rating here.

Sourcing

Frequently asked questions

Where can I buy A9F07401 and how do I get a price?

The A9F07401 is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing.

What is A9F07401's breaking capacity at 415 V AC?

The A9F07401 has a breaking capacity of 70 kA Icu at 380–415 V AC under EN/IEC 60947-2, and 10 kA Icn at 400 V AC under EN/IEC 60898-1.

What standards does A9F07401 comply with?

It is dual-rated to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/commercial), with overvoltage category IV and pollution degree 3.

MPN
A9F07401