Schneider Electric Acti9 iC60H miniature circuit breaker, A9F07404, 4 A, C-curve, 4P, 70 kA Icu at 415 V AC, DIN-rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07404 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F07404 — Ratings
ParameterValue
Rated current (In)4 A
Poles configuration4P
Number of protected poles4
Breaking capacity70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)70 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F07404 — Protection
ParameterValue
Curve codeC
Trip unit technologyThermal-magnetic
Magnetic tripping limit8 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F07404 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F07404 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F07404 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F07404 is an Acti9 iC60H miniature circuit breaker rated 4 A with a C-curve, 4 poles, and a 70 kA Icu breaking capacity at 415 V AC.

Listed as current production.

Terminals accept 1–25 mm² rigid or 1–16 mm² flexible conductors; tightening torque is 2 N.m. The IP20 finger-safe front allows panel mounting without additional shrouding. A trip indicator and contact position indicator give local status without opening the door.

Frequently asked questions

What is the breaking capacity of A9F07404?

The A9F07404 has a 70 kA Icu at 415 V AC per EN/IEC 60947-2, and 15 kA Icn at 400 V AC per EN/IEC 60898-1.

Where can I buy A9F07404?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What standards does A9F07404 comply with?

It complies with EN/IEC 60947-2 and EN/IEC 60898-1, and is suitable for isolation per both standards.

MPN