Skip to main content
Schneider Electric A9F07604 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F07604 Acti9 iC60H MCB, 4 A, 1P+N, Curv

MPNA9F07604
Active

Schneider Electric Acti9 iC60H, miniature circuit breaker, A9F07604, 4 A, 1P+N, curve C, 70 kA Icu at 240 V AC, DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F07604 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC60H
Poles description1P + N
Number of protected poles1
Device applicationDistribution

Electrical & Protection

A9F07604 — Electrical & Protection
ParameterValue
Rated current (In)4 A
Tripping curve codeC
Magnetic tripping limit8 x In +/- 20 %
Breaking capacity (Icu / AIR)70 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles

Mounting & Connection

A9F07604 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width36 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom

Environmental

A9F07604 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529

Approvals

A9F07604 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1

Electrical

A9F07604 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

What this MCB does on the rail

The Schneider Electric A9F07604 is an Acti9 iC60H miniature circuit breaker rated 4 A, 1P+N, curve C, with a breaking capacity of 70 kA Icu at 220...240 V AC 50/60 Hz per EN/IEC 60947-2 and 10 kA Icn at 230 V AC per EN/IEC 60898-1. That 70 kA Icu figure means it handles high fault currents typical in industrial distribution panels without upstream coordination headaches — you can land it downstream of a transformer or a main breaker rated up to that level. The thermal-magnetic trip unit gives magnetic tripping at 8 x In +/- 20 %, so it clears short-circuit faults fast while riding through motor inrush on C-curve. Mounts on DIN rail, takes 4 module pitches (9 mm each), and the double terminals accept up to 25 mm² rigid or 16 mm² flexible — enough for a 4 A feeder in a control cabinet.

Overvoltage category IV suits main incoming panels. IP20 finger-safe terminals.

Frequently asked questions

What is the breaking capacity of A9F07604?

70 kA Icu at 220...240 V AC per EN/IEC 60947-2, and 10 kA Icn at 230 V AC per EN/IEC 60898-1.

What is the rated current and curve of A9F07604?

4 A, curve C.

What mounting and terminal specs does A9F07604 have?

DIN rail mount, 4 module pitches, double terminals accepting up to 25 mm² rigid or 16 mm² flexible.

Where can I buy A9F07604?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN
A9F07604