Skip to main content
Schneider Electric A9F08116 — 1-Pole MCB (DIN Rail)

Schneider Electric A9F08116 Acti9 iC60H MCB, 1P 16A D Curve

MPNA9F08116
Active

Schneider Electric Acti9 iC60H miniature circuit breaker, A9F08116, 1-pole, 16 A rated current, D curve, 42 kA Icu breaking capacity, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F08116 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
A9F08116 — Electrical & Protection
ParameterValue
Rated current (In)16 A
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F08116 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)2 N.m top or bottom
A9F08116 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F08116 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F08116 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The A9F08116 is a 1-pole Acti9 iC60H miniature circuit breaker rated 16 A with a D trip curve. Breaking capacity hits 42 kA Icu at 12–60 V AC (EN/IEC 60947-2) and 15 kA Icu at 220–240 V AC, so it clears hard faults in distribution panels where fault current runs high.

Dual-rated to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/ commercial), so it qualifies for both distribution and machine control panels. Isolation suitability is certified under both standards; the contact position indicator confirms open contacts visually.

IP20 finger-safe front, so it's fine inside an enclosed panel but not for wet-area installation.

Frequently asked questions

Where can I buy A9F08116 and how do I get a price?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

What is A9F08116's listed depth?

Depth is 78.5 mm.

What is A9F08116's range?

It belongs to the Acti9 range.

MPN
A9F08116