Schneider Electric A9F08163

A9F08163 Acti9 iC60H MCB, 63 A, 1P, Curve D, 42 kA

MPN A9F08163
Obsolete

Schneider Electric Acti9 iC60H miniature circuit-breaker, 1P, 63 A, curve D, 42 kA Icu at 12-60 V AC, 78.5 mm depth, 18 mm width, IP20.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F08163 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2

All specifications

A9F08163 additional specifications
ParameterValue
ColorWhite
Depth78.5 mm
Width18 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The A9F08163 is a 1-pole Acti9 iC60H miniature circuit-breaker rated 63 A with a D tripping curve. The 42 kA Icu at 12-60 V AC (per EN/IEC 60947-2) tells you it can safely interrupt a fault up to that level without upstream cascading; at 230 V AC the Icn is 10 kA per EN/IEC 60898-1, which is the domestic/light-commercial standard.

Mounts on DIN rail (EN 60715). The toggle and trip indicator are visible through the panel door.

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic). Pollution degree 3, overvoltage category IV. Suitability for isolation is confirmed under both standards. No earth-leakage protection built in — that is handled separately by a residual-current device upstream.

MPN
A9F08163