Schneider Electric A9F08163 — 1-Pole MCB (DIN Rail)

A9F08163 Acti9 iC60H MCB, 63 A, 1P, Curve D, 42 kA

MPNA9F08163
Obsolete

Schneider Electric Acti9 iC60H miniature circuit-breaker, 1P, 63 A, curve D, 42 kA Icu at 12-60 V AC, 78.5 mm depth, 18 mm width, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F08163 — Identification
ParameterValue
Product nameActi9 iC60
Product / component typeMiniature circuit-breaker
Product rangeActi9
Device short nameiC60H
Poles description1P
Number of protected poles1
Device applicationDistribution
A9F08163 — Electrical & Protection
ParameterValue
Rated current (In)63 A
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu / AIR)42 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 15 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 10000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)20000 cycles
A9F08163 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Mounting supportDIN rail
Width18 mm
Height91 mm
Depth78.5 mm
Tightening torque (by circuit)3.5 N.m top or bottom
A9F08163 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
A9F08163 — Approvals
ParameterValue
Conformity standardsEN/IEC 60947-2 EN/IEC 60898-1
A9F08163 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2

Product details

The A9F08163 is a 1-pole Acti9 iC60H miniature circuit-breaker rated 63 A with a D tripping curve. The 42 kA Icu at 12-60 V AC (per EN/IEC 60947-2) tells you it can safely interrupt a fault up to that level without upstream cascading; at 230 V AC the Icn is 10 kA per EN/IEC 60898-1, which is the domestic/light-commercial standard.

Mounts on DIN rail (EN 60715). The toggle and trip indicator are visible through the panel door.

Dual-certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic). Pollution degree 3, overvoltage category IV. Suitability for isolation is confirmed under both standards. No earth-leakage protection built in — that is handled separately by a residual-current device upstream.

Frequently asked questions

Where can I buy A9F08163?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of A9F08163?

42 kA Icu at 12-60 V AC, 30 kA at 100-133 V AC, 15 kA at 220-240 V AC per EN/IEC 60947-2; 10 kA Icn at 230 V AC per EN/IEC 60898-1.

What compliance documentation does Schneider provide for A9F08163?

The part is certified to EN/IEC 60947-2 and EN/IEC 60898-1. Tropicalisation class 2 per IEC 60068-1. RoHS/REACH declarations are available from the manufacturer upon request.

MPN
A9F08163