Skip to main content
Schneider Electric A9F08202 — 2-Pole MCB (DIN Rail)

Schneider A9F08202 Acti9 iC60H MCB, 2A D-Curve, 2P, 70kA

MPNA9F08202
Active

Schneider Electric Acti9 iC60H, A9F08202, miniature circuit breaker, 2 A rated, D curve, 2-pole, 70 kA breaking capacity at 415 V AC, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F08202 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameiC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F08202 — Electrical
ParameterValue
Rated current [In]2 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)DC AC
Network frequency50/60 Hz
A9F08202 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]70 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F08202 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F08202 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F08202 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F08202 is a 2 A rated, D-curve miniature circuit breaker from Schneider Electric's Acti9 iC60H series. The 2 A rating is the continuous thermal current; the thermal-magnetic trip unit protects the downstream conductors and equipment from sustained overloads and short circuits. Breaking capacity is the headline number for this part: 70 kA Icu at 415 V AC (per EN/IEC 60947-2), with an Icn of 10 kA at 400 V (per EN/IEC 60898-1). The 10 kA Icn is the service breaking capacity under the domestic-standard 60898-1 test sequence; the 60947-2 rating governs industrial distribution.

Snap-on DIN rail mounting, 36 mm wide (4× 9 mm pitches), 91 mm tall, 78.5 mm deep. Two-pole configuration (2P) with protected poles on both paths. IP20 finger-safe terminals — suitable for enclosed panel installation, not for wet or washdown environments.

Frequently asked questions

Where can I buy A9F08202 and how do I get a price?

The A9F08202 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance documentation does Schneider provide for A9F08202?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with IP20 per IEC 60529, tropicalisation class 2 per IEC 60068-1, and suitability for isolation per both standards. The manufacturer provides the standard declaration of conformity and product certificate for these marks.

What is A9F08202's listed depth?

The depth is 78.5 mm.

What is the D curve on this breaker for?

The D curve (magnetic trip at 12× In ±20 %) is designed for circuits with high inrush currents — motor loads, transformers, or welding equipment — where a B or C curve would trip on startup.

MPN