Skip to main content
Schneider Electric A9F08203 — 2-Pole MCB (DIN Rail)

Schneider Electric A9F08203 Acti9 iC60H MCB, 3 A, D Curve, 2

MPNA9F08203
Active

Schneider Electric Acti9 iC60H, miniature circuit-breaker, 3 A, D curve, 2P, 70 kA Icu at 240 V AC, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F08203 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameiC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F08203 — Electrical
ParameterValue
Rated current [In]3 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)DC AC
Network frequency50/60 Hz
A9F08203 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]70 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F08203 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F08203 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F08203 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

At 3 A rated, it protects a circuit drawing up to 3 A continuous; the 70 kA Icu at 240 V AC tells you it can safely interrupt a fault current up to 70 kA without failing, which is essential for high-fault-capacity panels (e.g., near a large transformer or in an industrial distribution board). It is certified to both EN/IEC 60898-1 (household/industrial MCB standard) and EN/IEC 60947-2 (industrial circuit-breaker standard), so it qualifies for commercial and light industrial distribution panels — not just residential load centers. The 500 V AC rated insulation voltage (Ui) and overvoltage category IV mean it's rated for main incoming supply positions, not just downstream sub-circuits.

Deployment context

The toggle handle provides local on/off control and a trip-indicator flag for quick fault identification on the panel door.

Frequently asked questions

What is A9F08203's breaking capacity?

It has a breaking capacity of 70 kA Icu at 220–240 V AC 50/60 Hz per EN/IEC 60947-2, and 10 kA Icn at 400 V AC per EN/IEC 60898-1.

What is the D curve on this breaker?

The D curve means the magnetic trip operates at 12 x In ±20% — designed for loads with high inrush current like motors and transformers.

Where can I buy A9F08203?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
A9F08203