Skip to main content
Schneider Electric A9F08263 — 2-Pole MCB (DIN Rail)

Schneider Electric A9F08263 Acti9 iC60H MCB, D Curve, 63 A,

MPNA9F08263
Obsolete

Schneider Electric Acti9 iC60H miniature circuit breaker, A9F08263, D curve, 63 A rated current, 2 poles, 42 kA breaking capacity, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9F08263 — Identification
ParameterValue
Product nameActi9 iC60
Series / familyActi9
Device short nameiC60H
Product / component typeMiniature circuit-breaker
Device applicationDistribution
A9F08263 — Electrical
ParameterValue
Rated current [In]63 A
Number of protected poles2
Pole configuration2P
Network type (AC/DC)AC DC
Network frequency50/60 Hz
A9F08263 — Protection
ParameterValue
Tripping curve codeD
Magnetic tripping limit12 x In +/- 20 %
Breaking capacity (Icu)42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity [Ics]21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC
Energy limitation class3 conforming to EN/IEC 60898-1
Suitable for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Overvoltage categoryIV
Trip unit technologyThermal-magnetic
Earth-leakage protectionSeparate block
Operating / control typeToggle
Mechanical durability (cycles)20000 cycles
A9F08263 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height91 mm
Depth78.5 mm
Mounting supportDIN rail
Terminal connectionsDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Local signalling / indicationTrip indicator
Contact position indicatorYes
A9F08263 — Environmental
ParameterValue
Operating temperature range-35...70 °C
Storage temperature range-40...85 °C
Relative humidity95 % at 55 °C
A9F08263 — Approvals
ParameterValue
Standards / complianceEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F08263 is an Acti9 iC60H miniature circuit breaker rated 63 A with a D tripping curve, 2 poles, and a breaking capacity of 42 kA Icu at 12–133 V AC.

At 220–240 V AC the Icu is 30 kA, and at 380–415 V AC it is 15 kA — still robust for most industrial panel feeds. The 60947-2 rating gives it Category A utilisation and pollution degree 3, so it is suited for controlled environments with some conductive contamination.

Deployment context

Terminals accept 1–35 mm² rigid or 1–25 mm² flexible conductors; torque to 3.5 N·m. IP20 protection means it is for indoor, dry locations only — no washdown exposure.

Frequently asked questions

How do I get current pricing and availability for A9F08263?

Submit an RFQ through this listing. The part is sourced to order; pricing and stock are confirmed at quote time.

What is the breaking capacity of the A9F08263?

The A9F08263 has a breaking capacity of 42 kA Icu at 12–133 V AC, 30 kA at 220–240 V AC, 15 kA at 380–415 V AC, and 10 kA at 440 V AC per EN/IEC 60947-2, plus 15 kA Icn at 400 V AC per EN/IEC 60898-1.

What compliance documentation does Schneider provide for A9F08263?

The breaker is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with tropicalisation class 2 per IEC 60068-1. It is suitable for isolation per both standards.

MPN