Skip to main content
Schneider Electric A9F08401 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F08401 Acti9 iC60H MCB, D Curve, 1 A, 4

MPNA9F08401
Obsolete

Schneider Electric Acti9 iC60H, A9F08401, miniature circuit breaker, D curve, 1 A, 4 poles, 70 kA breaking capacity, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F08401 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F08401 — Ratings
ParameterValue
Rated current (In)1 A
Poles configuration4P
Number of protected poles4
Breaking capacity70 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)70 kA 100 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 70 kA 100 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 50 kA 100 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F08401 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60898-1 Yes conforming to EN/IEC 60947-2
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F08401 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8
A9F08401 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F08401 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The A9F08401 is a Schneider Electric Acti9 iC60H miniature circuit breaker with a D tripping curve, rated 1 A, 4 poles, and a 70 kA breaking capacity at 220–415 V AC. The 70 kA Icu at 415 V AC (per EN/IEC 60947-2) tells you this breaker can safely interrupt a fault up to that level without upstream damage; the 15 kA Icn at 400 V (per EN/IEC 60898-1) is the domestic-grade rating. Dual certification means it passes both the industrial (60947-2) and residential (60898-1) standards, so it qualifies for distribution panels in commercial or light industrial builds.

Deployment context

Snaps onto DIN rail (mounting support per) for panel integration.

Frequently asked questions

What are the key ratings of the A9F08401?

Rated current 1 A, D curve (magnetic trip at 12 x In), 4 poles, breaking capacity 70 kA Icu at 415 V AC per EN/IEC 60947-2, and 15 kA Icn at 400 V per EN/IEC 60898-1.

Where can I buy the A9F08401?

The A9F08401 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What compliance documentation does the A9F08401 carry?

Dual certified to EN/IEC 60947-2 and EN/IEC 60898-1. Tropicalisation class 2 per IEC 60068-1. Pollution degree 3 per EN/IEC 60947-2. Suitable for isolation per both standards.

MPN
A9F08401