Skip to main content
Schneider Electric A9F08425 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F08425 Acti9 iC60H MCB, 25 A, 4P, D Cur

MPNA9F08425
Obsolete

Schneider Electric Acti9 iC60H miniature circuit breaker, A9F08425, 25 A rated current, 4 poles, D tripping curve, breaking capacity 42 kA Icu at 12-133 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F08425 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution
A9F08425 — Ratings
ParameterValue
Rated current (In)25 A
Poles configuration4P
Number of protected poles4
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)DC AC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F08425 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F08425 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...25 mm² rigid Double terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8
A9F08425 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F08425 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F08425 is an Acti9 iC60H miniature circuit breaker rated for 25 A continuous current across four protected poles, with a D tripping curve that holds 12× In (±20 %) before the magnetic trip fires. The part is dual-rated to EN/IEC 60898-1 (domestic-grade Icn of 10 kA at 400 V AC) and EN/IEC 60947-2 (industrial-grade Icu up to 42 kA at 12-133 V AC), so it qualifies for both residential distribution boards and industrial panel builds.

Breaking capacity and isolation

The iC60H frame delivers 42 kA Icu at 12-133 V AC, 30 kA at 220-240 V AC, and 15 kA at 380-415 V AC per EN/IEC 60947-2. At 400 V AC the IEC 60898-1 Icn is 10 kA. The 4P version isolates all poles simultaneously, with a contact-position indicator and a trip-flag for local signalling.

IP20 finger-safe front. The thermal-magnetic trip unit is field-non-adjustable, so the 25 A rating is fixed; earth-leakage protection requires a separate Vigi block.

Frequently asked questions

What is the breaking capacity of the A9F08425?

The breaking capacity varies by voltage: 42 kA Icu at 12-133 V AC, 30 kA at 220-240 V AC, 15 kA at 380-415 V AC, and 10 kA Icn at 400 V AC per EN/IEC 60898-1.

How do I get a price and lead time for the A9F08425?

Submit an RFQ through the distributor. Pricing and availability are confirmed at quote time — the part is sourced to order against your request.

What standards does the A9F08425 comply with?

It complies with EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic), with suitability for isolation confirmed under both.

MPN
A9F08425