Skip to main content
Schneider Electric A9F08440 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F08440 Acti9 iC60H MCB, 40 A, 4P, D Cur

MPNA9F08440
Active

Schneider Electric Acti9 iC60H, miniature circuit breaker, 40 A, 4P, D curve, 42 kA Icu at 12-133 V AC, DIN rail mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F08440 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F08440 — Ratings
ParameterValue
Rated current (In)40 A
Poles configuration4P
Number of protected poles4
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F08440 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F08440 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F08440 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F08440 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F08440 is an Acti9 iC60H miniature circuit breaker rated at 40 A with a D tripping curve, four protected poles, and a breaking capacity of 42 kA Icu at 12–133 V AC (50/60 Hz) per EN/IEC 60947-2.

The D curve (magnetic trip at 12 x In ±20 %) means this breaker tolerates high inrush currents — typical for motor loads, transformers, or welding equipment — without nuisance tripping. The 40 A continuous rating and 4-pole configuration suit it for three-phase distribution with a switched neutral, common in European panel builds. Breaking capacity is derated by voltage: 42 kA at 12–133 V AC, 30 kA at 220–240 V, 15 kA at 380–415 V, and 10 kA at 440 V. The 10 kA Icn at 400 V per EN/IEC 60898-1 is the standard for domestic/commercial distribution; the higher Icu figures per 60947-2 cover industrial fault levels. For a 40 A feeder in a 400 V panel with a prospective fault current under 10 kA, this breaker is a clean fit. Thermal-magnetic trip technology with a separate earth-leakage block option means the A9F08440 handles overload and short-circuit protection on its own; add a Vigi iC60 module downstream if residual-current protection is needed. The isolation suitability mark (per both 60947-2 and 60898-1) confirms it can be used as a disconnecting means.

Deployment context

The 78.5 mm depth fits flush in most 100 mm deep enclosures.

Frequently asked questions

Where can I buy the A9F08440 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a quote request; availability and current pricing are confirmed at quote time.

What is the breaking capacity of the A9F08440 at 400 V?

At 400 V AC, the A9F08440 carries a 10 kA Icn per EN/IEC 60898-1 and a 15 kA Icu per EN/IEC 60947-2.

What compliance standards does the A9F08440 meet?

It is certified to EN/IEC 60947-2 and EN/IEC 60898-1, with suitability for isolation per both standards. Pollution degree 3 and overvoltage category IV are rated per 60947-2.

MPN
A9F08440