Skip to main content
Schneider Electric A9F08463 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F08463 Acti9 iC60H MCB, 63 A, D Curve,

MPNA9F08463
Active

Schneider Electric Acti9 iC60H, A9F08463, miniature circuit breaker, 63 A, D curve, 4P, 42 kA Icu at 12-133 V AC, DIN rail.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

A9F08463 — Identification
ParameterValue
Product nameActi9 iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
Device applicationDistribution

Ratings

A9F08463 — Ratings
ParameterValue
Rated current (In)63 A
Poles configuration4P
Number of protected poles4
Breaking capacity42 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 30 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)21 kA 50 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 50 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 15 kA 100 % conforming to EN/IEC 60947-2 - <= 250 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV

Protection

A9F08463 — Protection
ParameterValue
Curve codeD
Trip unit technologyThermal-magnetic
Magnetic tripping limit12 x In +/- 20 %
Earth-leakage protectionSeparate block
Suitability for isolationYes conforming to EN/IEC 60947-2 Yes conforming to EN/IEC 60898-1
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles

Mechanical

A9F08463 — Mechanical
ParameterValue
Mounting supportDIN rail
Control typeToggle
Terminal connection typeDouble terminal (top or bottom) 1...35 mm² rigid Double terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque3.5 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width72 mm
Height91 mm
Depth78.5 mm
Number of 9 mm pitches8

Environmental

A9F08463 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1

Approvals

A9F08463 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F08463 is a 4-pole Acti9 iC60H miniature circuit breaker rated at 63 A with a D trip curve. The 42 kA Icu at 12-133 V AC (30 kA at 220-240 V, 15 kA at 380-415 V, 10 kA at 440 V) tells you the interrupting capacity at the fault level — if your panel's prospective short-circuit current stays under those values, this breaker clears the fault without welding contacts or cascading upstream. It is certified to both EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (domestic/similar) standards, so it qualifies for distribution boards and industrial sub-panels alike. The 4 protected poles suit 3-phase + neutral circuits where you need overcurrent protection on all four paths.

Panel integration — DIN rail, 8 module pitches, IP20

The 72 mm width equals 8 x 9 mm pitches, so it occupies eight module positions in a distribution board. Strip length is 14 mm.

Durability and environmental ratings

Rated for 10,000 electrical cycles and 20,000 mechanical cycles — sufficient for a distribution breaker that sees infrequent switching. Overvoltage category IV — suitable for the main incoming supply point where transient overvoltages are highest.

Frequently asked questions

What is the breaking capacity of the A9F08463 at 400 V?

The breaking capacity is 15 kA Icu at 380-415 V AC and 10 kA Icu at 440 V AC per EN/IEC 60947-2. Under EN/IEC 60898-1, the Icn is 10 kA at 400 V AC.

What does the D curve mean on this MCB?

The D curve has a magnetic trip threshold of 12 x In ±20 %. That means the instantaneous trip activates at roughly 756 A (12 x 63 A) — designed to pass motor inrush currents without nuisance tripping while still clearing hard faults.

MPN
A9F08463