Skip to main content
Schneider Electric A9F43325 — Miniature Circuit Breakers (MCB)

Schneider Electric A9F43325 iC60N MCB, 25A 3P B-Curve, Acti9

MPNA9F43325
Obsolete

Schneider Electric Acti9 iC60N miniature circuit breaker, A9F43325, 25 A, 3-pole, B-curve, 36 kA breaking capacity, thermal-magnetic trip, clip-on DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

A9F43325 — Identification
ParameterValue
Product nameDisbo iC60
Product rangeActi9
Product/component typeMiniature circuit-breaker
A9F43325 — Ratings
ParameterValue
Rated current (In)25 A
Poles configuration3P
Number of protected poles3
Breaking capacity36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 100...133 V DC conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
Rated service breaking capacity (Ics)27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V DC
Rated operational voltage (Ue)12...133 V AC 50/60 Hz 220...240 V AC 50/60 Hz 380...415 V AC 50/60 Hz 440 V AC 50/60 Hz <= 180 V DC
Rated insulation voltage (Ui)500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Network type (AC/DC)AC/DC
Network frequency50/60 Hz
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Overvoltage categoryIV
A9F43325 — Protection
ParameterValue
Curve codeB
Trip unit technologyThermal-magnetic
Magnetic tripping limit4 x In +/- 20 %
Earth-leakage protectionSeparate block
Limitation class3 conforming to EN/IEC 60898-1
Electrical durability (cycles)10000 cycles
Mechanical durability (cycles)20000 cycles
A9F43325 — Mechanical
ParameterValue
Mounting supportRail
Mounting modeClip-on
Control typeToggle
Terminal connection typeSingle terminal (top or bottom) 1...25 mm² rigid Single terminal (top or bottom) 1...16 mm² flexible
Terminal tightening torque2 N.m top or bottom
Wire stripping length14 mm for top or bottom connection
Contact position indicatorYes
Local signalling/indicationTrip indicator
Width54 mm
Height85 mm
Depth78.5 mm
Number of 9 mm pitches6
A9F43325 — Environmental
ParameterValue
Operating ambient temperature-35...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Relative humidity95 % at 55 °C
Tropicalisation class2 conforming to IEC 60068-1
A9F43325 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60898-1

Product details

The Schneider Electric A9F43325 is an Acti9 iC60N miniature circuit breaker rated at 25 A with a B-curve trip characteristic, 3 poles, and a thermal-magnetic trip unit.

Breaking capacity is the headline differentiator here: 36 kA Icu at 12–133 V AC, 20 kA at 220–240 V, 10 kA at 380–415 V, and 6 kA at 440 V AC per EN/IEC 60947-2. The Icn rating under 60898-1 is 6000 A at 400 V. For DC circuits, it clears 10 kA at 100–133 V DC. The B-curve (4 x In magnetic trip, ±20%) gives it a wider magnetic-trip window than C or D curves, so it tolerates inrush from resistive loads and long cable runs better than a C-curve would.

Mounts via clip-on to a DIN rail (35 mm), occupying 6 x 9 mm pitches (54 mm wide). The 78.5 mm depth and 85 mm height fit standard distribution board cutouts. Terminals accept 1–25 mm² rigid or 1–16 mm² flexible wire; torque to 2 N·m. IP20 finger-safe terminals are standard for enclosed panels. A separate earth-leakage block (Vigi iC60) can be added on the right side for RCD protection.

Frequently asked questions

What is A9F43325's breaking capacity at 415 V?

At 380–415 V AC, the A9F43325 clears 10 kA Icu per EN/IEC 60947-2. The Icn rating under 60898-1 is 6000 A at 400 V.

What compliance standards does the A9F43325 meet?

It is certified to EN/IEC 60947-2 (industrial) and EN/IEC 60898-1 (residential/light commercial). Pollution degree 3, overvoltage category IV, tropicalisation class 2 per IEC 60068-1.

Where can I buy the A9F43325?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN